EM-7513  Rev.8  P. 4 / 5

 

SELECTING DIP SW (coarse adjustment)

INPUT TYPE

Choose Current or Voltage according to Table 2.

INPUT RANGE

Choose the desired range matching the maximum value 
and the span according to Table 3.

• 

For a current input, convert the range to a voltage with 
the following equation:

Table 2 

 = ON

INPUT TYPE

SW1

1

Current

Voltage

     

Voltage = (100% Current – 0% Current) 

×

 250 Ω

• 

When the 0% and 100% values have the same polarity, select the absolute greater value as Span.

• 

When the 0% and 100% values have opposite polarity, select the absolute difference of the two values (100% – 0%) as Span.

• 

If the Span value is available in two range selections, select the smaller range.  (e.g. Set to the 1 V range for 0 – 1 V, though 
the maximum value 1 V can be selectable both in 2 V and 1 V range.)

• 

The minimum span and offset requirements in the table must be met when choosing the desired range.

Table 3 

 = ON

MAX. VALUE OF

USABLE RANGE

SPAN

OFFSET

SW1

SW2

2

3

4

5

6

7

8

7

8

100 V

20 V ≤ Span ≤    100 V

-100 to +80% 

of the selected range

  20 V

4 V ≤ Span ≤      20 V

  10 V

2 V ≤ Span ≤      10 V

    2 V

400 mV ≤ Span ≤        2 V

    1 V

200 mV ≤ Span ≤        1 V

200 mV

40 mV ≤ Span ≤ 200 mV

100 mV

20 mV ≤ Span ≤ 100 mV

  20 mV

4 mV ≤ Span ≤   20 mV

OFFSET

See Table 4.
The offset is defined by the following equation:

Offset =

[0% Input]

× 100 (%)

[Max. value of usable range: Table 3]

Table 4 

 = ON

OFFSET

SW2

1

2

3

4

+60% < Offset ≤  +80%

+30% < Offset ≤  +60%

+10% < Offset ≤  +30%

-10% ≤ Offset ≤  +10%

-30% ≤ Offset <   -10%

-60% ≤ Offset <   -30%

-100% ≤ Offset <   -60%

GAIN

See Table 5.
The gain is defined by the following equation:

Gain =

[Max. value of usable range: Table 3]

× 100 (%)

[100% Input – 0% Input]

Table 5 

 = ON

GAIN

SW2

5

6

270% < Gain ≤    500%
150% < Gain ≤    270%

100% ≤ Gain ≤    150%

 

EXAMPLE

Calibrated input range: 1 – 5 V DC

1) Input type: According to Table 2, choose ‘Voltage.’
 

 Set SW1-1 to OFF.

2) Input range: 
  5 V > 1 V 

 5 V is used as the maximum value.

  According to Table 3, choose ‘10 V.’
 

 Set SW1-4 to ON.

3) Offset

1 V

×

 100 = 10 (%)

10 V

 

 According to Table 4, SW2-2 and SW2-3 to ON.

4) Gain

10 V

×

 100 = 250 (%)

5 V – 1 V

 

 According to Table 5, set SW2-6 to ON.

ON

1

SW2

2 3 4 5 6 7 8

ON

1

SW1

2 3 4 5 6 7 8

 

ZERO & SPAN ADJUSTMENTS (fine adjustments)

Referring to ‘ADJUSTMENT PROCEDURE,’ apply 0% and 
100% input signals and adjust the Zero to have 4 mA output 
and Span to have 20 mA output respectively.