EM-1609 Rev.15 P. 2 / 5
POINTS OF CAUTION
■
POWER INPUT RATING & OPERATIONAL RANGE
Locate the power input rating marked on the product and
confirm its operational range as indicated below:
■
AC Power
M2: 100 – 240 V AC, 50 – 60 Hz, maximum 6 VA
(85 – 264 V AC, 47 – 66 Hz)
■
DC Power
R: 24 V DC (24 V ±10%), maximum 3.5 W
P: 110 V DC (85 – 150 V), maximum 3.5 W
■
GENERAL PRECAUTIONS
Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.
■
ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■
AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
• Never use the internal relay under any load that exceeds
the rated contact values including the switching capaci-
ties (contact voltage and contact current).
Otherwise it will impair prescribed performance (insula-
tion failure, contact welding, contact failure) and cause
burning of the Relay itself.
COMPONENT IDENTIFICATION
Body
Specifications
Base Socket
Connection Diagram
Input Resistor
INPUT SPECIFICATIONS
■
DC Current
: 0 – 50 mA DC; shunt resistor attached to
input terminals (0.5 W)
Operational range: 0 – 70 mA DC (with 100 Ω / 0.5 W)
Minimum increment: 0.1 mA
Default setting: 4 – 20 mA DC
■
DC Voltage
: -1 – +1 V DC for S1;
-10 – +10 V DC for S2
Operational range: -1.15 – +1.15 V DC for S1;
-11.5 – +11.5 V DC for S2
Minimum increment: 10 mV for S1; 100 mV for S2
Default setting: -1 – +1 V DC for S1;
-10 – +10 V DC for S2
OUTPUT SPECIFICATIONS
■
Quad Alarm
Relay rating: 120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
■
Dual Alarm
Relay rating: 120 V AC @ 5 A (cos ø = 1)
240 V AC @ 2.5 A (cos ø = 1)
30 V DC @ 5 A (resistive load)
■
Small load current type
Relay rating: 30 V DC @ 1 A (resistive load)
INSTALLATION
Detach the yellow clamps located at the top and bottom of
the unit to separate the body from the base socket.
■
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
Shape and size of the base socket
are slightly different with various
socket types.
DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bot-
tom. Position the upper hook
at the rear side of base socket
on the DIN rail and push in
the lower. When removing the
socket, push down the DIN
rail adaptor utilizing a minus
screwdriver and pull.
■
2-M4
or
4.5(.18)
dia. hole
40±0.2
MOUNTING HOLES
(TOP VIEW)
WALL MOUNTING
• Install using M4 screw with re-
ferring to the right dimension.
• Install by screw that is securely
fastened or equivalent means.