CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

  Be sure to short the secondary side of CT or turn off the 

current at its primary side for preventing the CT from 

burning when the cables are to be disconnected from in-

put terminals of the base socket.

4) Alarm operations:  Check the alarm operations referring 

to the figure below.

5) Output load:  Check that the output load is 380 V AC / 

120 VA or 125 V DC / 30 W (≤ 0.5 A for CE) at the maxi-

mum.  For maximum relay life with inductive load, exter-

nal protection is recommended.

0

50

100

Input
(%)

LL

L

HH

H

L2 (1–2)

ON

L3 (1–3)

ON

L4 (9–11)

ON

OFF

OFF

L1 (9–10)

ON

OFF

OFF

Alarm Trip Operation                   

Terminal No. in parentheses

Example with quad N.O. contacts (LL, L, H, HH)

Trip Operation in Power Failure

• Output code 2: All relays turn off.
• Output code 3: All relays turn on.
• Output code 5: Terminals 1 – 3, 9 – 11 turn on.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.

• H (HH) Setpoint

   Increase the input signal from a value lower than the set-

point and check that the relay trips at the H (or HH) set-
point within the setpoint accuracy described in the data 
sheet.

• L (LL) Setpoint

   Decrease the input signal from a value higher than the 

setpoint and check that the relay trips at the L (or LL) 
setpoint within the setpoint accuracy described in the 
data sheet.

When the setpoints are shifted, please contact M-System’s 
Sales Office or representatives.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.