manualshive.com logo in svg
background image

AS4CT

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-1603  Rev.7  P. 2 / 4

FRONT VIEW & PROGRAMMING

 

L1

L2

L3

L4

ALARM

DATA

ITEM

DATA

ITEM

ITEM No. Display

DATA UP-DOWN Keys

ITEM No. UP-DOWN Keys

*

Monitor LEDs

DATA Display

*

L3 or L4 does not turn on for dual output type.

PROGRAMMING PROCEDURE

1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2) Press DATA UP or DOWN key and choose “1” or “2” on DATA 

display.

  1: Only alarm setpoints are modifiable.
  2: All parameters are modifiable.
3) Press ITEM UP or DOWN key until ITEM display shows the 

ITEM No. you need to change.

4) Press DATA UP or DOWN key and choose a DATA No. or value 

you need on DATA display.

5) Repeat above 3 and 4.  (Entered data is stored when you move to 

a new ITEM.)

6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “0” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.  

DATA display shows process input.

(You can now check data setting by choosing ITEM No.)

    Note: DO NOT press UP and DOWN keys simultaneously.

ITEM

MDF.

CODE 

DATA

CONTENTS

DEFAULT SETTING

P

N/A

-1999 – 9999

Process input display in engineering unit (as set in ITEM 07/08)

----

L1
L2
L3
L4

1, 2
1, 2
1, 2
1, 2

-1999 – 9999*

1

-1999 – 9999*

1

-1999 – 9999*

1

-1999 – 9999*

1

L1 alarm setpoint in engineering unit
L2 alarm setpoint in engineering unit
L3 alarm setpoint in engineering unit *

2

L4 alarm setpoint in engineering unit *

2

Quad: 20.0
Quad: 30.0
Quad: 70.0
Quad: 80.0

Dual: 20.0
Dual: 80.0

01

0, 1, 2

Modification code
0: Data indication only.
1: Only ITEM L1 – L4 are modifiable.
2: All parameters are modifiable.

1

02

N/A

0 – 99

Status indication (“0” is normally indicated.)
0: Normal  1: Memory error  10: Out of input range -15 – +115%

03

N/A

6, 7

Input range  6: S1, 7: S5

Specified when ordering

04

N/A

-15.0 – 115.0

Input indicated in % (as set in ITEM 27, 28)

----

05
06

2
2

-19.99 – 99.99

0.000 – 9.999

Zero adjustment (%) (fine adj. of the value set in ITEM 27)
Gain adjustment (fine adj. of the value set in ITEM 28)

0.00
1.000

07

2

-1999 – 9999

Display range scaling 0%
of the range set in ITEM 27/28.  ITEM 07 < ITEM 08

0.0

08

2

-1999 – 9999

Display range scaling 100%
of the range set in ITEM 27/28.  ITEM 07 < ITEM 08

100.0

09

2

0, 1, 2, 3

Decimal point position
(Specify the number of 
digits) 

0: _ _ _ _
1: _ _ _ . _
2: _ _ . _ _
3: _ . _ _ _

1

10

2

0 – 99

Power ON-delay time (seconds)

5

11

2

0 – 99

Alarm ON-delay time (seconds)

0

12

2

0, 1, 2, 3, 4

Moving average (sampling cycle: 100 msec.)
0: No, 1: 4 samples, 2: 8 samples, 3: 16 samples, 4: 32 samples

0

13
14
15
16

2
2
2
2

0, 1
0, 1
0, 1
0, 1

L1 trip operation 
L2 trip operation 
L3 trip operation 
L4 trip operation 

(0: Lo, 1: Hi)
(0: Lo, 1: Hi)
(0: Lo, 1: Hi) *

2

(0: Lo, 1: Hi) *

2

Quad: 0
Quad: 0
Quad: 1
Quad: 1

Dual: 0
Dual: 1

17

2

0, 1 – 60

Power-saving mode
0 : Continuous display after the last access*

3

1 – 60 : Time before display turned off (minutes)

10

18
19
20
21

2
2
2
2

0, 1
0, 1
0, 1
0, 1

L1 coil at alarm     (0: Energized, 1: De-energized)
L2 coil at alarm     (0: Energized, 1: De-energized)
L3 coil at alarm     (0: Energized, 1: De-energized)*

2

L4 coil at alarm     (0: Energized, 1: De-energized)*

2

0
0
0
0

22

N/A

----

Version No. indication

----

23
24
25
26

2
2
2
2

1 – 9999
1 – 9999
1 – 9999
1 – 9999

L1 hysteresis (deadband) in engineering unit
L2 hysteresis (deadband) in engineering unit
L3 hysteresis (deadband) in engineering unit *

2

L4 hysteresis (deadband) in engineering unit *

2

1.0
1.0
1.0
1.0

Отзывы: