WIRING INSTRUCTIONS
■
SCREW TERMINAL
Torque: 0.6 N·m
CHECKING
Open the unit’s outdoor enclosure cover when you conduct
checking of the transmitter. Be sure to close the cover after
the checking is complete.
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check current with an ammeter. Be sure that the
connected transmitter allows the load shown in the fol-
lowing table.
MODEL
EQUIVALENT INPUT IMPEDANCE
6BSN-A
230Ω plus output load
6BSN-H
90Ω plus output load × 0.16
3) Output: Check that output load is within the permissible
limit shown in the following table.
MODEL
LOAD RESISTANCE
6BSN-A
50 – 350Ω
6BSN-H
50 – 600Ω
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained below.
Zero and Span adjustments are located behind the top cover
of the unit. Open the enclosure cover, release the knurled
knobs at the front of the unit and open the top cover.
After the calibration is complete, be sure to close both cov-
ers.
1
2
3
4
5
6
VR1
VR2
■
HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the input signal on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0% with the
VR1.
2) SPAN: Apply 100% input and adjust output to 100% with
the VR2.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.
6BSN
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8869 Rev.1 P. 5 / 5