M-system 48NDVA Скачать руководство пользователя страница 9

48NDVA

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9441-A  Rev.9  P. 9 / 9

 

SIMULATED OUTPUT

1) Hold down [DOWN] for longer than 5 seconds to enter 

the simulation mode until the Z and S indicators start 

blinking, and the digital indicator shows ‘000.0,’ blinking.

2) Press [UP] or [DOWN] buttons to simulate a desired DC 

output.  Digital indicator is programmable from ‘000.0’ to 

‘100.0’ %*

2

.

3) Hold down [SET] for longer than 5 seconds to get out of 

the simulation mode.

*1.  The [M] button remain activated for 1 minute after it 

has been used to choose a indicator LED (programming 
mode).  During this period, pressing the [M] button briefly 
is enough to choose another indicator.  After 1 minute, it 
turns to deactivated state.

*2. The bargraph goes off.

CALIBRATION PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the indication to a receiving instrument or in 
case of regular calibration, adjust the output as explained 
in the following.

 

HOW TO CALIBRATE THE OUTPUT INDICATION

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust the bargraph, digital 

indicator and DC output to 0% following the each proce-

dure explained in “ADJUSTMENT PROCEDURE.”

2) SPAN:  Apply 100% input and adjust the bargraph, digi-

tal indicator and DC output to 100% following the same 

procedure.

3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular checking procedure is explained below:

 

CHECKING

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the bargraph, 
digital indicator and DC output for the respective input sig-
nal remains within accuracy described in the data sheet. 
When the bargraph, digital indicator and DC output are out 
of tolerance, recalibrate the unit according to the “CALI-
BRATION PROCEDURE” explained earlier.

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.6 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protectors for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Содержание 48NDVA

Страница 1: ...cted wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity In order to enable the operator to turn off the power in put immediately install a switch or a circuit breaker ac cording to the relevant requirements in ...

Страница 2: ...STERED MOUNTING Not conform to degree of protection IP65 1 0 61 5 min USING BEZELS Bezels are used when the unit needs to be adapted to an ex isting panel cutout It is not required when the panel cutout size is as specified in the unit s data sheet 31 5 138 mm Three types of bezels are selectable when ordering Standard type Fits into M System s 48 Series panel cutout 38 139 5 mm Option D type Fits...

Страница 3: ...nd below the unit for ventilation Bracket TERMINAL CONNECTIONS Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit EXTERNAL DIMENSIONS unit mm inch 75 2 95 103 4 06 10 39 18 71 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 16 M3 SCREW TERMINALS 2 M3 SCREWS 144 5 67 137 5 5 41 4 1 16 36 1 42 31 1 22 100 3 94 Rounded corners for the option D OPTION D BEZEL 3 ...

Страница 4: ...mm etc STANDARD BEZEL 2 10 4 41 7 5 30 3 9 15 136 5 5 37 144 5 67 11 4 45 7 5 30 4 9 19 136 5 5 37 144 5 67 8 5 33 10 4 41 7 5 30 136 5 5 37 144 5 67 OPTION F BEZEL 4 CONNECTION DIAGRAM 1 2 12 13 14 INPUT 15 16 7 8 9 ALARM OUTPUT CODE 2 2 points 1 2 INPUT 5 6 5 6 1 2 INPUT 5 6 15 16 ALARM OUTPUT CODE 0 None ALARM OUTPUT CODE 4 4 points 12 13 14 15 16 LLa 11 La LLb Lc LLc 8 9 10 HHa 7 Hc HHc HHb Ha...

Страница 5: ...olor code 2 orange green green red red red H L 50 40 30 20 10 0 10 20 30 40 50 m3 h mA 100 SET H S P Z L 90 80 70 60 50 40 30 20 10 0 SET ENTER Button H Setpoint Adj Alarm Function Span Adj Setting Decimal Point Position Moving Average Brightness Adj Zero Adj Setting L Setpoint Adj Alarm Function Setting UP Button Switcing Detailed Settings Mode Setting Selector Setting DOWN Button Switcing Detail...

Страница 6: ...ay for L Setpoint Increase Decrease Complete Digital Indicator SET L LL M Press at once ON Time Delay for LL Setpoint Increase Decrease Complete Digital Indicator SET LL Z M Press at once Zero Adjustment Digital Indicator Bargraph Z SET Z M Increase Decrease Zero Adjustment Digital Indicator Only Complete Z ON LED OFF SPAN ADJUSTMENT Apply 100 input signal before adjustment All alarm setpoints wil...

Страница 7: ... is set to 7 the brightest level 3 Keep pressing DOWN button at least for 5 seconds to enter the simulated output mode 4 Pressing UP or DOWN button simulates the output between 000 0 and 100 0 5 Keep pressing SET button at least for 5 seconds to exit the simulated output mode Note Each setting sequence is complete only when SET button is pressed Once set parameters are not lost even after the powe...

Страница 8: ...before H as the H setpoint can not go above the HH setpoint How to Cancel LL and L Alarms 1 Press UP or DOWN buttons until the indicator comes to the lower limit digital indicator shows and press SET LL indicator must be set before L as the L setpoint can not go below the LL setpoint LL or L H HH 1 2 ALARM ON TIME DELAY 1 Hold down M for 3 seconds 1 and push M to choose LL 2 Press UP and DOWN butt...

Страница 9: ...vel Turn the power supply on and warm up for more than 10 minutes 1 ZERO Apply 0 input and adjust the bargraph digital indicator and DC output to 0 following the each proce dure explained in ADJUSTMENT PROCEDURE 2 SPAN Apply 100 input and adjust the bargraph digi tal indicator and DC output to 100 following the same procedure 3 Check ZERO adjustment again with 0 input 4 When ZERO value is changed ...

Отзывы: