P. 5 / 16

EM-9507-B  Rev.6

SETTING PROCEDURE

POWER ON

■ 

GENERAL SETTING FLOWCHART

*

1. Optional settings for parameters in a broken-line section.

 

Alarm Setting Mode is locked with no-alarm-output type. 

POWER ON

*

1

 

INITIAL SETTING FLOWCHART

Initial Setting Complete

Measuring Started

Hold down Scale/    button for 3 seconds or more to move on to Scaling Setting Mode.

Choose an input type and display scale values.

Hold down Alarm/    button for 3 seconds or more to move on to Alarm Setting Mode.

Go through the alarm settings.

Hold down Alarm/   + Scale/    buttons at once for 3 seconds or more 

to move on to Advanced Setting Mode.  Go through the advanced settings.

Hold down Alarm/    button or Scale/    button for 1 second or more

to go back to Measuring Mode.

If necessary, hold down Max/Min Alarm/    buttons at once

for a preset time duration to enter Lockout Setting Mode.

Go through the lockout settings.

Measuring Mode

Hold down Alarm/    or Scale/    button 

for ≥1 second

Hold down Scale/    button

for ≥3 seconds

Measuring

Measuring stopped

*

3

Mode transition

*

1. Preset time can be specified with “Transition Time to Lockout Setting Mode” in Advanced Setting Mode.

*

2. Alarm Setting Mode is locked with no-alarm-output type. 

*

3. The last measured values or status are held for DC and alarm outputs while the measuring is stopped.

 

(Except the analog output adjustments during the loop test and the scaling)

Scaling Setting Mode

Alarm Setting Mode

Advanced Setting Mode

Hold down Alarm/    or Scale/   

button for ≥1 second

Hold down Alarm/    or Scale/    button 

for ≥1 second

Hold down Max/Min + Alarm/    buttons at once

for a preset time duration

*

1

 

Hold down Alarm/   + Scale/    buttons at once

for ≥3 seconds

Lockout Setting Mode

Hold down Alarm/    or Scale/    button 

for ≥1 second

Hold down Alarm/    button

for ≥3 seconds

Loop Test Output Mode

Hold down Alarm/    or Scale/    button 

for ≥1 second

Hold down Alarm/   + Scale/    + Shift buttons at once

for ≥5 seconds

*

2

Содержание 47LCT

Страница 1: ...ate it POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 50 60 Hz approx 6 5VA 24...

Страница 2: ...tripped HH turns on when the HH alarm is tripped P turns on when none of the other alarms is tripped 3 Function indicators Indicate setting modes and status 4 Max Min button Used to switch the main d...

Страница 3: ...packing must be in place to hold the meter Do not remove it 1 Insert the unit into the panel cutout 2 Push the mounting brackets into the grooves on both sides of the rear module until they hit the p...

Страница 4: ...T H OUTPUT L OUTPUT H OUTPUT HH OUTPUT 9 10 POWER U V ALARM SUFFIX CODE 2 SPDT contact 2 points 9 10 POWER U V ALARM SUFFIX CODE 0 No alarm output 7 8 DC OUTPUT 7 8 DC OUTPUT 7 8 DC OUTPUT Note The se...

Страница 5: ...out Setting Mode Go through the lockout settings Measuring Mode Hold down Alarm or Scale button for 1 second Hold down Scale button for 3 seconds Measuring Measuring stopped 3 Mode transition 1 Preset...

Страница 6: ...hin the scaled range The command cannot be executed when the operation is prohibited with the lockout protection setting MAX MIN display mode cannot be cancelled while in the Forced Zero mode Forced Z...

Страница 7: ...N Shift Alarm Alarm Analog Output 0 Adj UP DOWN Alarm Shift Alarm Alarm Alarm Analog Output Action at Force Zero Display DISP SCALE Shift OPERATIONS IN SETTING MODES Main display The main display show...

Страница 8: ...ion the parameters will return to the default values Input Scaling Value A Enter the desired zero value 0 Input scaling value A Input scaling value B Input Scaling Value B Enter the desired full scali...

Страница 9: ...utton to move on to Input scaling value A 3 Zro and Tch indicators turn on 4 Zero point Press Up button and Tch indicator starts blinking 5 Apply 5 input signal Press Up button again and Tch indicator...

Страница 10: ...Alarm Setting Mode Alarm Shift L Setpoint L Deadband L ON Delay Time 19999 19999 0000 9999 00 99 Shift Shift Alarm Alarm Alarm Alarm Alarm Alarm L Coil at Alarm RYEN RYDN Shift Alarm Alarm Shift L Tri...

Страница 11: ...B B HH ON Delay Time 00 99 Shift Alarm Alarm Alarm Alarm HH Coil at Alarm RYEN RYDN Shift Alarm Alarm Shift HH Setpoint 19999 19999 Shift H Setpoint H Deadband H ON Delay Time 19999 19999 0000 9999 00...

Страница 12: ...H Lo trip H coil at alarm H Coil energized at alarm H Fnc H Coil de energized at alarm D P H Fnc H P Fnc HH setpoint HH deadband hysteresis HH ON delay time HH ON delay time seconds HH Deadband hyster...

Страница 13: ...e button at once for 3 seconds Hold down Alarm or Scale button for 1 second Shift Shift Alarm Alarm Alarm Alarm Alarm Alarm Alarm Shift Alarm Alarm Advanced Setting Mode Version Indication Display Ref...

Страница 14: ...manually from the setting mode Transition time to Lockout Setting Mode The display goes to Lockout Setting Mode only when the designated buttons are pressed for the specified time duration 1 F00 0 25...

Страница 15: ...out Setting Mode in Advanced Setting Mode A Scale Scale Scale Scale Scale Scale Set value Setting Parameters A Forced Zero Lockout OFF ON Shift Alarm Alarm PARAMETER Alarm setting lockout Lock Alarm S...

Страница 16: ...on repairing in the factory may be required Non volatile memory error writing Increase decrease the input signal until it is back within the measuring range While the error message is on the display p...