47DM OPERATING MANUAL EM-9510-B Rev.6
35. APPENDICES
35.1 SPECIFICATIONS
■
GENERAL SPECIFICATIONS
Construction
Panel flush mounting
Degree of protection
IP66; Applicable to the front of the panel meter mounted according to the specified
panel cutout.
Connection
Input, excitation supply,
DC output, relay output,
network interface, power
M3 separable screw terminal (torque 0.6 N·m)
Photo MOSFET relay,
event trigger input
Euro Type Connector Terminal
Applicable wire size: max. 1.3 dia., 0.5 – 1.25 mm
2
, stripped length 7 to 8 mm
BCD output
50-pin connector (Honda Tsushin Kogyo HDR-EC50LFDT1-SLE+)
Screw terminal
Nickel-plated steel (standard) or stainless steel
Housing material
Flame-resistant resin (gray)
Isolation
Input or excitation supply to DC output to HH output or H output to L output or LL
output to network or BCD output or event trigger input to power
Infrared communication
Transmission distance max. 1 meter (for use with the COP-IRU)
Setting (front button)
Scaling setting mode
Input scaling value Zero and Span, display scaling value Zero and Span, decimal
point position, bargraph type, bargraph lower limit, bargraph upper limit, analog
output type, analog output function mode, analog output 0%, analog output 100%,
analog output 0% adjustment, analog output 100% adjustment
Alarm setting mode
Bank No., alarm output pattern, HH, H, L and LL alarm setpoint, HH, H, L and LL
trip action, HH, H, L and LL deadband (hysteresis), HH, H, L, LL and P ON delay
time, HH, H, L, LL and P OFF delay time, HH, H, L, LL and P one-shot output, HH,
H, L, LL and P coil at alarm, main display blinking at alarm, bank copy
Advanced setting mode
Event trigger mode, ON timing delay, OFF timing delay, startup timer, averaging
type, averaging time, low-end cutout, low-end cutout value, display color, automatic
return time to Measuring Mode, transition time to Lockout Setting Mode, display
refreshing rate, manual sub display reset, P output, latching alarm, alarm power
ON delay, standby sequence, scaling error, round off low-digit reading, display
reading type, high-pass filter, backlight brightness, LCD contrast, bank switching,
REQ input logic, DAV output logic, DATA output logic, status output logic, firmware
version indication
Lockout setting mode
Alarm setting lockout, scaling setting lockout, advanced setting lockout, Modbus
setting lockout, MAX/MIN display control lockout, forced zero control (Up button)
lockout, loop test output lockout, IR communication lockout, Modbus communica-
tion lockout, initialization
Modbus setting mode
Device address, baud rate, parity bit, stop bit, T1.5 timer, T3.5 timer, long register
Loop test output
----
Read rate
20 times/sec. (50 msec.)
Averaging
Simple average, moving average or no averaging
Lockout setting
Prohibiting certain operations; protecting settings
■
DISPLAY
Main display
5½ digits, LCD with LED backlight, 7-segment, 14.2 mm (.56) high
Color
Red or green changeable at alarm
Scaling range
-20000 to 100000
Decimal point position
10
-1
, 10
-2
, 10
-3
, 10
-4
, or none
Zero indication
Higher-digit zeros are suppressed
Sub display
7 digits, LCD with LED backlight, 7-segment, 5.5 mm (.22) high
Color
Green
Over-range indication
‘-20000’ or ‘100000’ blinking for display values out of the scaled range (decimal
point position depending upon setting).
‘S.ERR’ (main display) and ‘UNDER’ or ‘OVER’ (sub display) blinking when the
input signal is out of the usable range.
Bargraph
No. of LED segments
20, displayed with divided by 10
Color
Amber