11.4 STANDBY SEQUENCE
The alarm and DC outputs can stand by until the input enters P zone from power on, which is called standby sequence.
“Output immediately at the startup” (‘OFF’) or “output standing by until the input enters P zone” (‘ON’) can be selected. The
default setting is “output immediately at the startup”.
IMPORTANT
• Do not set the ON delay time when the standby sequence is set to ‘ON’.
• The changes on this setting are effective after power off and restart.
11.4.1 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the specifications and settings.
1
Hold down Alarm/
↓
and Scale/
↑
buttons at once for 3 seconds
or more to move on to Advanced Setting Mode.
• The averaging type is indicated.
• The SD indicates ‘AVE-TP’.
NOTE
With the I/O option code ‘6’ or ‘A’, the event trigger mode is indicated (‘EVENT’ on the SD).
2
Press Alarm/
↓
or Scale/
↑
button to go to the standby sequence
setting.
• The standby sequence is indicated.
• The SD indicates ‘STDBY’.
3
Press Shift and Up buttons to select the standby sequence.
• Select ‘OFF’ or ‘ON’.
1,2,
4,5
1,2,
4,5
3
3
Blinking