manualshive.com logo in svg
background image

27PM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7657-A  Rev.2  P. 3 / 3

FUNCTION MONITOR LED (option /M)

 

FUNCTION MONITOR LED

3

2

4

1

+

Function 

Monitor LED

 

INPUT MONITOR: 

The input 0 – 100% is converted into a combination of 1-second (1 unit) and 0.25-second (0.2 unit) cycled 

pulses.  1 unit corresponds to 25%, while 0.2 unit corresponds to 5%.  0% equals to 1 unit, while 100% cor-
responds to 5 units.  The input % is represented in the total number of 1-unit pulses and 0.2-unit pulses, 
repeated in the sequence of ‘1-unit pulses ––> 0.2-unit pulses ––> OFF for 1 second or more.’

[Examples]

25% = 2 units

30% = 2.2 units

45% = 2.8 units

50% = 3 units

100% = 5 units

0% = 1 unit

1 second

1 UNIT

25%

ON OFF

1 sec.

0.2 UNIT

5%

0.25 sec.

 

ERROR MONITOR: 

Indicates the transmitter’s error status.

Lower overrange

:  The input signal is lower than the out-

put’s lower range limit.

2 sec. cycle

0.125 sec. OFF

Upper overrange

:  The input signal is higher than the out-

put’s upper range limit.

0.125 sec. OFF - ON - OFF

2 sec. cycle

Burnout

: Sensor wire breakdown is detected.

0.125 sec. ON - OFF

Internal error

: The CPU detects an internal error.

0.125 sec. ON - OFF - ON

1 sec. cycle