INSTRUCTION  MANUAL

MODEL

10RS/10RK

RTD TRANSMITTER

COMPONENT IDENTIFICATION

INSTALLATION

Use Standard Rack (model: 10BX

).

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the
connection diagram label on the unit side.

CHECKING

1) Terminal wiring:  Check that all cables are correctly

connected according to the connection diagram.

2) Power input voltage:  Check voltage supplied to the rack

(model: 10BX

).  For the DC power source, be sure that

the ripple level is within 10% p-p.

3) Input:  Check voltage across the terminal 1 – 2 with a

sensitive voltmeter.
(With 20

°

C or 68

°

F, approx. 220mV with Pt 100

, approx.

110mV with Pt 50

.)

If RTD wires are broken, the output goes over 100% (below
0% with downscale protection) due to burnout protection
function.  Check leadwires in such a case.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

Zero Adj.

Span Adj.

Output 1

Body

Specification Label

Connection Diagram

Label

(side)

Zero Adj.

Output 2

*

Span Adj.

Terminal Cover

*

Provided only when the second output is selected.

BEFORE USE ....

Thank you for choosing M-System.  Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.

■ 

PACKAGE INCLUDES:

Signal conditioner ................................................... (1)

■ 

MODEL NO.

Check that model No. described on specification label is
exactly what you ordered.

■ 

INSTRUCTION MANUAL

This manual describes necessary points of caution when you
use this product, installation, connection and basic mainte-
nance procedures.

POINTS OF CAUTION

■ 

POWER INPUT RATINGS

• Power input ratings are specified by the model number
suffix code.  Check the power input voltage for the unit on the
specification label.

24V DC 

±

10%, approx. 35mA with Voltage Output 1

approx. 55mA with Current Output 1

■ 

GENERAL

• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.

■ 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration.  Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +55

°

C (23

to 131

°

F) with relative humidity within 30 to 90% RH in order

to ensure adequate life span and operation.

■ 

WIRING

• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present.  Do not install them in the same duct.

■ 

AND ....

• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.

+

1

OUTPUT 1

7

8

+

OUTPUT 2

5

6

CONNECTOR

*

1 output type has the output 1 connected to the 

  card-edge connector in parallel.

OUTPUT 2

*

POWER

2

A

B

B

RTD

3