background image

10JV

P. 4 / 4

EM-0862 Rev.4

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty.  To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

MAINTENANCE

Regular calibration procedure is explained below:

■ 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%,
50%, 75% and 100% input signal.  Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of
tolerance, recalibrate the unit according to the "ADJUST-
MENT PROCEDURE" explained earlier.

[GROUP 01]

ITEM

INPUT DATA

EXAMPLE (DEFAULT)

CONTENTS

01

S

0, 1

MTSW : MON MODE

Modification code
0  : Data indication only.
1  : All parameters are modifiable.

02

P

Alphanumeric

TG : XXXXXXXXXX

Tag name entry (10 characters max.)

03

P

Number (%)

OUTPER  XXX.XX

Output status monitor (%) & simulation output

05

D

No input

INPPER  XXX.XX

Input status monitor (%)

06

D

No input

INPVAL XXX.XX

Input status monitor in actual value, same unit as selected in ITEM 10.

10

TYPE OF TRANSMITTER INPUT

D

11

mV-1: 5 – 100mV

D

12

mV-2: 0.05 – 1V

P

13

mV-3: 0.5 – 10V

P

14

mV-6: 1 – 5V

D

15

mV-A: 4 – 20mA

D

16

mV-H: 10 – 50mA

11

P

COARSE INPUT RANGE SELECTION

mV-1

mV-2

mV-3

mV-6 / A / H

(

±

 mV)

(

±

 V)

(

±

 V)

0

INPRNG: XXXX

    5

0.05

  0.5

1

INPRNG: XXXX

  10

0.10

  1.0

No Adjustment

2

INPRNG: XXXX

  20

0.20

  2.0

Needed

3

INPRNG: XXXX

  50

0.50

  5.0

4

INPRNG: XXXX

100

1.00

10.0

14

P

Actual value

SCLLOW XXXXXX

Input range scaling 0% value

15

P

Actual value

SCLHIG XXXXXX

Input range scaling 100% value
Use the same enginering unit as the coarse range selected in ITEM 11.

19

P

Percentage

FINZER

Fine zero adjustment
Initial status shows actual bias (%).
When data is entered, output (%) is shown.

20

P

Percentage

FINSPN

Fine span adjustment
Initial status shows actual gain (%).
When data is entered, output (%) is shown.

Modification Code

D:  No modification (writing) possible.  Used only for monitoring (reading).
S:  Modifiable at any time.
P:  Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.

PROGRAMMABLE ITEMS

The following items can be monitored and programmed.  For detailed explanations, please refer to the Operation Manual for
Model PU-2

 (EM-9255), Section A.

MDF.

CODE