10JV
P. 3 / 4
EM-0862 Rev.4
CHECKING
1) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2) Power input voltage: Check voltage supplied to the rack
(model: 10BX
❑
). For the DC power source, be sure that
the ripple level is within 10% p-p.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibra-
tion, unless you need to match the signal to a receiving
instrument or conduct regular calibration.
Zero and span are adjusted with using the Programming
Unit (model: PU-2
❑
). Also, fine adjustments for the Output
2 can be done with the potentiometers on top of the unit which
are accessible using Extender Card (model: 10EC) maintain-
ing electrical connection to the rear connector.
Refer to the Operation Manual for Model PU-2
❑
for explana-
tions how to use the programmer.
■
WARNING ON USE OF THE PROGRAMMING UNIT
• Be sure to disconnect the Programming Unit before you
turn on/off power supply to the unit.
■
HOW TO CALIBRATE THE OUTPUT 1
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
•
Fine Output Calibration
Using the Programming Unit (ITEM 19, 20)
ITEM 19 is for Zero, and ITEM 20 is for Span.
1) Turn the unit into Program mode (ITEM 01).
2) Apply simulated 0% input. Increase/decrease values (de-
fault: 0%) at ITEM 19 until the output signal is calibrated
to actual 0%.
3) Apply simulated 100% input. Increase/decrease value
(default: 100%) at ITEM 20 until the output signal is
calibrated to actual 100%.
4) Apply simulated 0% input again and check 0% output.
5) When 0% value is changed, repeat the above procedure 2)
- 4).
The 0% value may be shifted when the output span is
greater than the input span (gain
≥
1).
■
HOW TO CALIBRATE THE OUTPUT 2
Use Extender Card (model: 10EC) to access the Output 2
Adjustments on top of the unit.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above procedure
1) – 3).