16
List of Property Numeric Value Range Restrictions
Object name
Object Type
Minimum range
value
Maximum
range value
Default value
RoomTemp
**
Numeric
-40.0°F (-40°C)
122.0°F (50°C)
N/A
OutdoorTemp
**
Numeric
-39.0°F (-40°C)
122.0°F (50°C)
N/A
RoomHumidity
**
Numeric
10% 90% N/A
SupplyTemp
Numeric
-40.0°F (-40°C)
122.0°F (50°C)
N/A
SupplyRH
Numeric
0% 100%
N/A
OccCoolSetpoint
Numeric
54°F (13°C)
100°F (37°C)
As per Stat
OccHeatSetpoint
Numeric
40°F (4.5°C)
90°F (32°C)
As per Stat
StandByCoolSetpoint
Numeric
54°F (13°C)
100°F (37°C)
As per Stat
StandByHeatSetpoint
Numeric
40°F (4.5°C)
90°F (32°C)
As per Stat
UnoccCoolSetpoint
Numeric
54°F (13°C)
100°F (37°C)
As per Stat
UnoccHeatSetpoint
Numeric
40°F (4.5°C)
90°F (32°C)
As per Stat
DehumidRHSetpoint
Numeric
15%
95%
As per Stat
HumidificationRHSetpoint
Numeric
10%
90%
As per Stat
EffectiveHumidificationRHSetpoint
Numeric
10%
90%
As per Stat
HumidificationHighLimitSetpoint
Numeric
50%
90%
As per Stat
PIHeatingDemand
Numeric
0% 100%
N/A
PICoolingDemand
Numeric
0% 100%
N/A
HumidifierOutput Numeric
0% 100%
N/A
EconomizerOutput Numeric
0% 100%
N/A
**
Room Temperature, Outdoor Temperature and Room Humidity need to be set Out Of Service if you want to write to
the object present value. When Out Of Service is set to "True", the thermostat local present value will be derived from
the wireless network instead of the present value at the thermostat.
List of Property Enumeration Sets for BV Objects
Object Name
Object
Type
Inactive_Text
Active_Text
Default value
AuxCommand Boolean
Off On Off
DehumidStatus Boolean
Off On Off
GFanStatus
Boolean
Off On Off
W2Stratus
Boolean
Off On Off
W1Status
Boolean
Off On Off
Y1Status
Boolean
Off On Off
Y2Status
Boolean
Off On Off
ReversingValveStatus
Boolean
Off On Off
AuxStatus
Boolean
Off On Off
DI1Status
Boolean
Not Activated
Activated
Not Activated
DI2Status
Boolean
Not Activated
Activated
Not Activated
BI1Status
Boolean
Deactivated Activated Not
Activated
BI2Status
Boolean
Deactivated Activated Not
Activated
UI3Status
*
Boolean
Not Activated
Activated
Not Activated
PIRmotionStatus
Boolean
Not Activated
Activated
Not Activated
* This object is linked to UI3 input on all VT7200 and VT7300 series thermostat when used in binary mode. The Not
Activated / Activated flag status is changed upon a local contact closing on the input and will also result in the
SupplyTemp Numeric to respond from one end of its range to the other.