Problem
Possible Cause
Possible Remedy
Chiller cools
well below the
desired Set-
Point
Microprocessor programmed
incorrectly
Malfunctioning solenoid valve
Solid State Relay failure
Microprocessor failure
Reprogram microprocessor - Call
Lydall
Repair or replace solenoid valve
Replace Solid State Relay
Replace microprocessor
Chiller shuts
down during
operation
Refrigeration high pressure cut-out
set too low
Refrigeration low pressure cut-out
set too high
Water modulating valve set too high
Excess refrigerant charge
Pump overload setting too low
Pump overload tripped
Low voltage
Adjust and reset refrigeration high
pressure cut-out
Adjust and reset refrigeration low
pressure cut-out
Adjust water modulating valve
Remove excess refrigerant, then
charge with type and amount of
refrigerated listed on serial tag
Adjust and reset pump thermal
overload relay to specifications, or
replace if faulty
Determine cause, if pump is
damaged, repair or replace
Check electrical service to chiller
Too much
recirculating
pressure to
process
Flow control valve set too high
Pressure relief valve set too high
(unless not adjustable)
Throttle flow control valve
Adjust pressure relief valve
Compressor
does not run
Compressor internal thermostat
tripped
Defective Solid State Motor
Overload
Motor burned out
Allow time for compressor to cool
and automatically reset
Replace module
Replace - Call Lydall