Application

In the past, all emergency lights were left on 24 hours a day to meet safety codes.  Now  you  can 
specify  &  install  a 

UL924  Listed Emergency  Power  Control  LUT-ALCR-D-FM, 

which converts up 

a normal light fixture into an approved emergency light.  During  normal  operation,  the                      
LUT-ALCR-D-FM dims designated  emergency  lights  with the  same  control  as  your  normal lights.  
During a utility power interruption, the LUT-ALCR-D-FM turns designated emergency lights on, at full 
brightness, regardless of dimmer position.

Intended for use with switching, 0-10V and DALI/EcoSystem dimming controls.

To control multiple emergency luminaires from a single UL924 relay, use model LUT-ALCR-D.
For Line Voltage Dimmable Loads, use model LUT-ATS-D.
For applications using 10 or more high inrush electronic ballasts or drivers, highbay or 347V 
applications, use EPC-1-D-HV.

Patented Automatic Diagnostic - 

When the room switch is turned off,  LUT-ALCR-D-FM tests itself for 

2.5 seconds, testing  that  an  emergency  power  source  is  available  and  that  the  LUT-ALCR-D-FM, 
ballast, and lamp(s) are functioning  correctly.   This  feature  eliminates  the  need  for  manual  monthly 
testing and is approved for this purpose.  This allows installation in any location because its test switch 
does not need to be accessible.  This feature can be disabled in the field by cutting the blue jumper.

Fire Alarm / Remote Test Switch - 

Some applications demand that emergency lighting be activated 

upon fire alarm, security alarm, or remote test switch activation.  The LUT-ALCR-D-FM is equipped 
with a low voltage override input (red jumper).  Please visit www.lvscontrols.com/FAI.php for details