o
Replace the tightening device with the spare accessory and screw it by means
of a 9 mm wrench;
o
Screw the protection cap, manual knob, thermostatic head or thermoelectric
head back.
To adjust the flow rate:
o
Unscrew the
ABS plug “A” where the gasket “B” is placed;
o
Without forcing, use a 5 mm Allen key to close the obturator “C”;
o
Open the obturator for a number of turns as indicated on the flow rate
diagram;
o
Screw back the ABS plug “A”.
WARNING
: Once the system has been leak tested, please relieve the pressure.
A differential pressure over 1 bar between the inlet and the outlet of the valve
may cause the sealing O-ring to be expelled.
Before starting the system it is important to check that:
o
All union
fittings marked with “12” are perfectly tightened;
o
The check valve marked with “5” is completely open. To adjust the valve,
unscrew the brass plug and act on the obturator by means of a 5 mm hex
wrench.
The value shown by the thermostatic head is indicative, the temperature of the water
entering the radiant panels circuit can be read on the thermometer of the upper
group.
To avoid excessive noise in the system, do not use the thermostatic valve with ΔP
values higher than 0,5 bar.
Coupled with the pump PCE 755 art. 69011560, the GM 1192 system can be
installed in a cabinet with a 90 mm internal usable depth.
~
Luxor S.p.A.
Sede amministrativa, stabilimento e uffici commerciali:
via Madonnina, 94
– 25018 Montichiari - (BS) Italy
Administrative office, factory and commercial office:
Tel.: 030-9961161
– Fax: 030-9961165
– www.luxor.it
Luxor si riserva il diritto di apportare miglioramenti e modifiche ai prodotti descritti ed ai relativi dati tecnici in qualsiasi momento e senza preavviso -
Luxor reserves the right to ameliorate and modify the above products and their technical data at any time and without notice