LIMITATIONS

The unit should be installed in accordance with all National, State and
Local Safety Codes and the limitations listed below:

1. Limitations for the indoor unit, coil, and appropriate accessories

must also be observed.

2. The outdoor unit must not be installed with any duct work in the air

stream. The outdoor fan is the propeller type and is not designed to
operate against any additional external static pressure.

3. The maximum and minimum conditions for operation must be

observed to ensure a system will give maximum performance with
minimal service.

4. The maximum allowable equivalent line length for this product is 80

feet.

Standard Lineset Applications

Maximum allowable lineset varies depending on the vertical separation
between the evaporator and condenser. See Table below for allowable
line set lengths and sizing.

Unit Reduced Capacity Conditions

Minimum / Maximum Operating Limit Conditions

AIR TEMPERATURE AT 

OUTDOOR COIL, ° F (° C)

AIR TEMPERATURE AT 

INDOOR COIL, ° F (° C)

Min.

Max.

Min.

Max.

DB Cool

DB Cool

WB Cool

WB Cool

35(2)*

125(52)*

57(14)

72(22)

*

Reference the NOTICE under the “Unit Reduced Capacity Conditions” 

 section.

Allowable Vertical Linesets

Model

Liquid 

Line

Suction 

Line

Max Line 

Length - 
Units on 

Equal Level

Max Suction 

Line Riser - If 

OD Unit is 

Above ID Unit

Max Liquid 

Line Riser - If 

OD Unit is 

Below ID Unit

24

3/8”

3/4”

80 feet

25 feet

25 feet

36

48

7/8”

60

NOTICE

Inverter Temperature Protection: 
If excessive inverter temperatures are sensed, the compressor speed
/ capacity is reduced until an acceptable condition is reached. 
When the inverter temperature returns to an acceptable level, the
system returns to normal operation.
Over / Under Current Protection: If a low or high Current Condition
is sensed, the compressor speed / capacity is reduced until an
acceptable current level is reached.
When the system reaches an acceptable current level, the compres-
sor and fan return to normal operating conditions.
Over / Under Voltage Protection: If a low or high supply Voltage
Condition is experienced (below 187 VAC or above 265 VAC), the
compressor speed / capacity is automatically reduced until an accept-
able voltage level is sensed.
When an acceptable voltage level is sensed, the system automati-
cally returns to a normal state of operation.
High Altitude Protection: If the unit is installed in Altitudes of 6,500
ft / 2,000 m above sea level or higher, the compressor and outdoor
fan reduce speeds to protect the system. It is not recommended
these units be installed at altitudes greater than 6,500 ft / 2,000 m
above sea level. 
Low Ambient Protection:
Cooling Mode:
 The unit automatically adjusts to maintain cooling
operation in outdoor ambient conditions down to 35° F (2° C). The
unit reduces capacity and Low Ambient Protection (cooling mode) or
cycles off if asked to provide cooling when the outdoor temperature is
at or below these conditions. 

Содержание ACCLIMATE AL21 Series

Страница 1: ...ng high quality appearance Charge Smart A built in touch screen instantly displays the system overall condition including the system pressures and refrigerant charge without the need to attach additio...

Страница 2: ...rranty when registered online within 90 days of installa tion Agency Listed Safety certified by CSA to UL 1995 CSA 22 2 Performance certified to ANSI AHRI Standard 210 240 in accordance with the Unita...

Страница 3: ...2 Rows Deep 1 1 2 2 Fins Inch 22 22 18 18 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Installed 3 3 4 3 4 7 8 7 8 Unit Charge Lbs Oz 4 7 8 7 6 14 9 15 1 Charge Per Foot...

Страница 4: ...the system charge without attaching a separate manifold gauge set or temperature sensors 6 Permanently mark the unit data plate with the total amount of refrigerant in the system SYSTEM CHARGE FOR VA...

Страница 5: ...r If OD Unit is Below ID Unit 24 3 8 3 4 80 feet 25 feet 25 feet 36 48 7 8 60 NOTICE Inverter Temperature Protection If excessive inverter temperatures are sensed the compressor speed capacity is redu...

Страница 6: ...0 19 05 Low 475 14 20 11 30 35 70 AL21B4821S AVV49DE321 24 5 High 1550 45 50 34 40 20 00 13 00 Med 800 25 20 18 50 19 10 Low 525 14 90 11 50 36 20 AL21B4821S MVC16CN21 21 0 CM49CE3A1 High 1450 45 50 3...

Страница 7: ...75 9 9 8 2 37 20 AL21B2421S LP9C060B12MP13C 17 5 CM25BE1A1 High 775 23 0 17 4 20 50 14 25 Med 475 13 8 10 8 19 05 Low 325 9 7 7 7 36 35 AL21B2421S LP9C080B12MP13C 17 5 CM25BE1A1 High 825 23 4 18 3 20...

Страница 8: ...C080B12MP13C 17 5 CM37BE2A1 High 1250 34 6 26 4 19 00 12 20 Med 725 18 9 15 4 18 15 Low 475 11 0 9 6 33 05 AL21B3621S LP9C080C16MP13C 21 0 CM37CE2A1 High 1125 34 8 25 6 19 25 13 00 Med 650 18 6 14 8 1...

Страница 9: ...LV120C20MP12C 21 0 CM49CE3A1 High 1525 45 5 33 2 19 50 12 50 Med 875 25 0 20 0 18 65 Low 675 14 4 11 1 34 05 AL21B4821S TP9C080C16MP13C 21 0 CM49CE3A1 High 1500 45 5 32 8 19 50 12 25 Med 775 25 0 19 1...

Страница 10: ...0C20MP12C 21 0 CM61CE4A1 High 1675 52 5 37 6 19 75 12 50 Med 1100 30 2 24 6 18 95 Low 825 20 6 17 8 35 95 AL21B6021S TM8V120C20MP12C 21 0 CM61CE4A1 High 1675 52 5 37 6 19 75 12 50 Med 1100 30 2 24 6 1...

Страница 11: ...0 6 17 8 35 95 AL21B6021S LP9C100C20MP13C 21 0 CM61CE4A1 High 1750 52 0 37 8 19 75 12 20 Med 1050 30 4 24 4 19 10 Low 700 20 4 16 3 37 05 AL21B6021S LP9C120D20MP13C 24 5 CM61DE4A1 High 1650 52 5 37 2...

Страница 12: ...icient inte rior unit access for removing the compressor through the side of the unit UNIT CONSTRUCTION Units shall be shipped completely wired piped and assem bled Wiring pigtails shall be provided f...

Страница 13: ...GHTXDWH ZDOO VXSSRUW 87 21 6SHFLDO FDUH PXVW EH WDNHQ WR DYRLG UHFLUFXODWLRQ RI GLVFKDUJH DLU WKURXJK RXWGRRU FRLO CAUTION Care must be taken to prevent ice from damaging the unit Damage may occur fro...

Страница 14: ...080 5 1 7 1 81 76 127 OHDUDQFH EHWZHHQ WZR XQLWV PD EH UHGXFHG WR PLQLPXP SURYLGHG WKH VHUYLFH DFFHVV FOHDUDQFH LV LQFUHDVHG WR PLQLPXP DQG WKH FOHDUDQFH RQ HDFK UHPDLQLQJ VLGH LV PDLQWDLQHG DW PLQLP...

Страница 15: ...6 14 6 15 3 15 5 17 0 19 1 KW 1 62 1 61 1 61 1 60 1 57 1 65 1 64 1 65 1 63 1 60 1 68 1 68 1 68 1 66 1 63 95 T C 20 0 21 5 21 5 24 7 27 1 20 8 22 4 22 5 25 3 28 3 21 6 23 2 23 4 25 9 29 5 S C 13 8 14...

Страница 16: ...5 2 86 2 88 2 89 2 90 2 85 2 87 2 94 2 95 2 96 2 86 2 87 105 T C 30 1 31 8 32 6 35 8 40 4 31 4 32 9 34 2 39 1 43 8 32 7 33 9 35 7 42 4 47 3 S C 20 5 21 4 21 7 24 0 26 6 21 3 22 0 22 2 25 4 28 6 22 1 2...

Страница 17: ...3 29 3 29 4 32 3 38 3 29 4 29 9 29 9 32 9 37 6 30 5 30 4 30 3 33 4 36 9 KW 4 58 4 60 4 60 4 65 4 72 4 67 4 68 4 68 4 73 4 79 4 76 4 77 4 76 4 82 4 85 115 T C 41 3 43 0 42 7 46 9 52 4 42 7 43 5 43 8 4...

Страница 18: ...56 4 60 4 59 4 62 4 62 4 65 4 69 4 69 4 71 4 71 4 75 4 79 95 T C 51 3 53 9 54 8 60 2 65 5 53 3 55 3 55 8 61 1 66 9 55 3 56 6 56 7 61 9 68 2 S C 35 9 37 9 37 9 41 7 45 9 37 1 38 8 38 7 42 5 46 8 38 2...

Отзывы: