temperature. [ON/UP = 2] The thermostat operates in the same manner
as above, however there are only two temperature program periods for
heating and cooling (DAY and NITE). This may be more convenient if you
are typically home during the day, and only need the set temperature to be
different while you are sleeping.
SWITCH #4 (SCALE):
[OFF/DOWN = F, default] All temperature values are
displayed using the Fahrenheit scale. [ON/UP = C] This setting displays
all temperature values using the Celsius scale.
SWITCH #5 (TIME):
[OFF/DOWN = 12 HR, default] This setting displays
the clock times and temperature program period start time values on the
screen using US standard AM and PM values. [ON/UP = 24 HR] This
setting displays the clock and temperature program period start time
values on the screen using the 24 HR military-time format (17:30 hours,
22:00 hours, without using AM/PM).
SWITCH #6 (DELAY):
[OFF/DOWN = 5 MIN, default] This sets the
minimum length of time that Heat or Cool must remain either On or Off,
before it will automatically switch to the alternate On or Off state. This
internal delay prevents rapid cycling of your system and provides
equipment protection particularly for cooling units. The 5-minute setting
is fine for most applications. [ON/UP = 2 MIN] If you feel that your
system may need to cycle more frequently than the thermostat is
allowing, then you may use the 2-minute setting.
SWITCH #7 (RECOVERY):
[OFF/DOWN = DISABLE, default] The Early
Recovery feature affects how the thermostat transitions from an energy
saving setback (DAY and NITE) program period, to a comfort (MORN and
EVE) program period temperature, when it is following the daily
temperature programs. When this is disabled, the thermostat makes a set
temperature change at the beginning of an upcoming period's start time.
[ON/UP = ENABLE] The Early Recovery feature will calculate the capability
of your system and turn on the heating or cooling early so that the
temperature in your home reaches the desired set point as close as
possible to the start of the period. During the time that the thermostat is
performing a recovery, the word “RECOV.” will be shown in the display
screen.
18