1.  First remove the bottom of the instrument. If necessary, 4 holes can be broken through for the mounting on 

the wall or at the ventilation duct. The breakthroughs should remain closed when assembling it at a ventilation 
duct through cable flanges. This is the only way to guarantee the housing tightness  

 
2.  In case of unevenness of the mounting wall, 4 spacers can be assembled.   
 
3.  Insert  the  appropriate  cables  into  the  membrane  which  is  at  the  bottom  of  the  instrument  by  piercing  small 

holes into the membrane with a pointed scriber and then push the cables (only simple isolation) through the 
holes.  

 
4.  Please use the stain relief plate for a cable stain relief. 
 
5.  After having set the dowels or drilled the appropriate holes in the wall, the bottom can be screwed.  
 
6.  Now you can screw the cables on the connector with the ferrule. Please consider for this the electric diagram 

of the designer, respectively of the instrument.   

 
7.  Check the wiring carefully, before connecting the plugs to the cover plate with integrated electronics.  

 

8.  Introduce the cover plate into the upper bracket and click it laterally on the bottom. Check the correct fitting. 
 
9.  After switching on the supply voltage the 

HTT-V

 

registers on the display. 

 
 

 

 

EMC note: 

1.  Disturbing circuits of measurement or analysis units have to be separated by open ground.  
2.  Avoid, wherever possible, the parallel motion of measurement connections and power electric cables.  
3.  Shield the measurement connections, if necessary, and connect the screen only on one side with a defined 

mass potential.  

4.  Twist the unshielded cables in pairs and keep them as short as possible.  
 

Recommended cabling: 

Supply: 24 VDC +/- 10% single-strands from 0.5...0.75 mm2 (22 ... 18 AWG) with PVC insulation or equivalent 2-
fold strand. 
AOUT: 0...10 VDC / 0... 20 mA 
Single-strand from 0.25...0.5 mm2 (24 ... 20 AWG) twisted and possibly shielded with PVC insulation or corre-
sponding 2/3/4-fold strand. 

 
 
 
 
 
 
 
 
 

Содержание 28896

Страница 1: ...ged 31 01 03 TT Document created changed 03 08 2012 Rea Revision Revision Draft released 18 02 03 DEL Document released 03 08 2012 Rea Jede unerlaubte Verwendung ist strafbar Any unpermitted use is su...

Страница 2: ...ns s 8 8 3 3 S SA AF FE ET TY Y 8 8 4 4 I IN NS ST TA AL LL LA AT TI IO ON N 8 8 5 5 M MO OU UN NT TI IN NG G 9 9 5 5 1 1 O Ou ut ts si id de e m me ea as su ur re em me en nt t 1 10 0 6 6 S ST TA AR...

Страница 3: ...e er ra at tu ur re e t tr ra an ns sm mi it tt te er r AN 28896 Humidity temperature transmitter type DigiControl HTT V S room with 24 VAC VDC power supply with LCD display with standard polyformalde...

Страница 4: ...use is subject to prosecution 1 1 2 2 A Ac cc ce es ss so or ri ie es s a an nd d s sp pa ar re e p pa ar rt ts s AN 28928 AN 28929 Sal_SC humidity set 58 75 Sal_SC humidity 90 AN 29025 AN 28904 Sal_S...

Страница 5: ...o prosecution AN 28902 AN 29121 Stainless steel probe duct HTT V M1 length of cable 3 m To use with high humidity 85 Stainless steel probe duct HTT V M2 length of cable 10 m To use with high humidity...

Страница 6: ...ogue outputs Special features Large LCD for a simultaneous display of RH and temperature Easy and intuitive menu navigation 3 keys 2 analogue outputs for measured value RH und temperature U or I freel...

Страница 7: ...temperature humidity 0 1 C 1 0 RH Measurement interval 330 500 ms Temperature effect on measurement typical 0 06 RH C Resolution of analog outputs typical 5 mV 5uA Accuracy of analog outputs typical 0...

Страница 8: ...alfunctions or errors can cause large material damage or personal injury additional precautions and external safety measures must be taken so that in case of an error defined operating conditions are...

Страница 9: ...ls or drilled the appropriate holes in the wall the bottom can be screwed 6 Now you can screw the cables on the connector with the ferrule Please consider for this the electric diagram of the designer...

Страница 10: ...rt the system check the correct supply wiring and the configuration of the analogue outputs U I switch Close the cover of the HTT V before the power supply is switched on Check the fuse protection on...

Страница 11: ...strafbar Any unpermitted use is subject to prosecution 6 6 1 1 C Co on nn ne ec ct ti io on ns s a e Analogue outputs b Power supply Connector for standard humidi ty probe c f Probe connection room d...

Страница 12: ...rical connections This connection must be made by a qualified technician To make the connection the transmitter must not be energized Power suppy connection Before making the connection you must first...

Страница 13: ...ptions for the application have to be configured For this the instrument has an intuitive menu guidance which is started by the key Enter Menu keys Operation ENTER ENTER Menu and submenus Press 2 seco...

Страница 14: ...he probe after having inspected visually and shaken the SAL SC Make sure that the cylinder is close to the probe Wait at least 30 minutes necessary for the balancing of the moisture inside the cylinde...

Страница 15: ...alues for Range L and Range H at the Transmitter HTT V for example 0 RH RLs and 100 RH RHs Set the desired output range 0 2 10V 0 4 20mA Set the control system in the same way 7 7 2 Measurement Enter...

Страница 16: ...e temperature and humidity can be overridden This override is active for 10 minutes then the system displays the current actual value of the temperature and humidity 7 7 1 11 1 P Pa as ss sw wo or rd...

Страница 17: ...e probe element SPACE CAL points are too close 2 0 RH RANGE Range exceeded Power Operating voltage outside the limits FATAL Fatal error DATA Not enough data for Moving Average Error messages A serious...

Страница 18: ...18 Draft created changed 31 01 03 TT Document created changed 03 08 2012 Rea Revision Revision Draft released 18 02 03 DEL Document released 03 08 2012 Rea Jede unerlaubte Verwendung ist strafbar Any...

Отзывы: