Luwa 28896 Скачать руководство пользователя страница 16

 

Operating Instruction

 

Q5.25.45

 

TLT

 

 

Page

 16 / 18 

Draft created/changed: 31.01.03/TT 

Document created/changed: 03.08.2012 / Rea 

Revision: - 

Revision: - 

Draft released: 18.02.03/DEL 

Document released: 03.08.2012 / Rea

 

Jede unerlaubte Verwendung ist strafbar / Any unpermitted use is subject to prosecution.

 

Temperature Unit 

*UNIT T 

Manual override 

*MANVAL 

Password protection 

*KEYLO 

Filter settings RH 

F. RH 

Exit Menu 

EXIT 

 
 

7

7

.

.

8

8

 

 

T

T

e

e

m

m

p

p

e

e

r

r

a

a

t

t

u

u

r

r

e

e

 

 

U

U

n

n

i

i

t

t

:

:

 

 

In this menu item you can change the unit temperature from °C (ISO unit) to the US format 
°F. The changeover is done by pressing the keys [ 

 ], [ 

 ]. 

 
 

7

7

.

.

9

9

 

 

L

L

o

o

w

w

-

-

p

p

a

a

s

s

s

s

f

f

i

i

l

l

t

t

e

e

r

r

 

 

s

s

e

e

t

t

t

t

i

i

n

n

g

g

:

:

 

 

 

Press [ENTER]. 

⇒  

The display starts flashing. Use [

] or [

] to set the low-pass filter between 0 and20. 

 

Press [ENTER] again for confirmation. 

 

Remark: 

 

The low-pass filter damps the measurement value display as well as the analogue output signal. This func-
tion can be used in case of big pressure oscillations. 

 

Basically it is recommended to set a low filter with high oscillations (high frequency) and a high filter with low 
oscillations (low frequency). 

 
 

7

7

.

.

1

1

0

0

 

 

M

M

a

a

n

n

u

u

a

a

l

l

 

 

o

o

v

v

e

e

r

r

r

r

i

i

d

d

e

e

:

:

 

 

In this menu item the actual value of the temperature and humidity can be overridden. This override is active for 
10 minutes, then the system displays the current actual value of the temperature and humidity.  
 
 

7

7

.

.

1

1

1

1

 

 

P

P

a

a

s

s

s

s

w

w

o

o

r

r

d

d

 

 

p

p

r

r

o

o

t

t

e

e

c

c

t

t

i

i

o

o

n

n

:

:

 

 

At shipping from factory the password is deactivated. You can activate the password (4 digits) on your own. 
 

Attention:

 The activation of the password is set by the code >< „

0000

“ and activating the menu “

Lock

“ , but 

latest after 2 minutes (without operation). Note your password. Password reset can only be done via the factory-
reset function. Thereby all configuration data will be deleted and the factory settings are taken over. 
 
Menu: *

KEYLO

 -> ENTER -> CODE -> ENTER -> Setting of the password -> [ 

 ] LOCK & ENTER -> Password 

activated 

*DONE*

 

 

Reset to factory settings: 
 

All parameters including the password code are reset to the factory settings. This function is activated as follows:  
 
• Switch off the supply voltage 
• Press and keep pushed the key [ 

 ] when the power supply is turned off and switch the power supply on again 

• Following text appears on the display: “

FA SET?

“ 

• Select with the keys [ 

 ], [ 

 ] “

YES

“ 

• “

DONE

“ is displayed and the instrument is restarted. The device is thus reset to factory settings.  

 
 

7

7

.

.

1

1

2

2

 

 

E

E

x

x

i

i

t

t

 

 

t

t

h

h

e

e

 

 

s

s

e

e

t

t

-

-

u

u

p

p

 

 

• In the Exit Menu press the  key, to change in the measurement mode. 
• press the [Enter] key for more than 2sec., at any menu level, for changing to the measurement mode. 
 
 

Содержание 28896

Страница 1: ...ged 31 01 03 TT Document created changed 03 08 2012 Rea Revision Revision Draft released 18 02 03 DEL Document released 03 08 2012 Rea Jede unerlaubte Verwendung ist strafbar Any unpermitted use is su...

Страница 2: ...ns s 8 8 3 3 S SA AF FE ET TY Y 8 8 4 4 I IN NS ST TA AL LL LA AT TI IO ON N 8 8 5 5 M MO OU UN NT TI IN NG G 9 9 5 5 1 1 O Ou ut ts si id de e m me ea as su ur re em me en nt t 1 10 0 6 6 S ST TA AR...

Страница 3: ...e er ra at tu ur re e t tr ra an ns sm mi it tt te er r AN 28896 Humidity temperature transmitter type DigiControl HTT V S room with 24 VAC VDC power supply with LCD display with standard polyformalde...

Страница 4: ...use is subject to prosecution 1 1 2 2 A Ac cc ce es ss so or ri ie es s a an nd d s sp pa ar re e p pa ar rt ts s AN 28928 AN 28929 Sal_SC humidity set 58 75 Sal_SC humidity 90 AN 29025 AN 28904 Sal_S...

Страница 5: ...o prosecution AN 28902 AN 29121 Stainless steel probe duct HTT V M1 length of cable 3 m To use with high humidity 85 Stainless steel probe duct HTT V M2 length of cable 10 m To use with high humidity...

Страница 6: ...ogue outputs Special features Large LCD for a simultaneous display of RH and temperature Easy and intuitive menu navigation 3 keys 2 analogue outputs for measured value RH und temperature U or I freel...

Страница 7: ...temperature humidity 0 1 C 1 0 RH Measurement interval 330 500 ms Temperature effect on measurement typical 0 06 RH C Resolution of analog outputs typical 5 mV 5uA Accuracy of analog outputs typical 0...

Страница 8: ...alfunctions or errors can cause large material damage or personal injury additional precautions and external safety measures must be taken so that in case of an error defined operating conditions are...

Страница 9: ...ls or drilled the appropriate holes in the wall the bottom can be screwed 6 Now you can screw the cables on the connector with the ferrule Please consider for this the electric diagram of the designer...

Страница 10: ...rt the system check the correct supply wiring and the configuration of the analogue outputs U I switch Close the cover of the HTT V before the power supply is switched on Check the fuse protection on...

Страница 11: ...strafbar Any unpermitted use is subject to prosecution 6 6 1 1 C Co on nn ne ec ct ti io on ns s a e Analogue outputs b Power supply Connector for standard humidi ty probe c f Probe connection room d...

Страница 12: ...rical connections This connection must be made by a qualified technician To make the connection the transmitter must not be energized Power suppy connection Before making the connection you must first...

Страница 13: ...ptions for the application have to be configured For this the instrument has an intuitive menu guidance which is started by the key Enter Menu keys Operation ENTER ENTER Menu and submenus Press 2 seco...

Страница 14: ...he probe after having inspected visually and shaken the SAL SC Make sure that the cylinder is close to the probe Wait at least 30 minutes necessary for the balancing of the moisture inside the cylinde...

Страница 15: ...alues for Range L and Range H at the Transmitter HTT V for example 0 RH RLs and 100 RH RHs Set the desired output range 0 2 10V 0 4 20mA Set the control system in the same way 7 7 2 Measurement Enter...

Страница 16: ...e temperature and humidity can be overridden This override is active for 10 minutes then the system displays the current actual value of the temperature and humidity 7 7 1 11 1 P Pa as ss sw wo or rd...

Страница 17: ...e probe element SPACE CAL points are too close 2 0 RH RANGE Range exceeded Power Operating voltage outside the limits FATAL Fatal error DATA Not enough data for Moving Average Error messages A serious...

Страница 18: ...18 Draft created changed 31 01 03 TT Document created changed 03 08 2012 Rea Revision Revision Draft released 18 02 03 DEL Document released 03 08 2012 Rea Jede unerlaubte Verwendung ist strafbar Any...

Отзывы: