Appendix
Default settings
67
© Lutz-Jesco GmbH 2014
Subject to technical changes.
140327
Solenoid-Diaphragm Dosing Pump
MAGDOS LP
Operating Instructions
BA-10231-02-V03
r/w = read/write, 1 address space = 1 word = 2 Bytes = 16 Bits
17.2 Default settings
Preset operating mode
Manual mode
(delivery capacity0 %)
90 - 91
High
r
Number
Status bit message
00000000
bin
00000010
bin
: List of messages deleted
Low
r
Number
0000 0000
bin
0000 0001
bin
: Container at minimum level
0000 0000
bin
0000 0010
bin
: Container at empty level
0000 0000
bin
0001 0000
bin
: Flowcon/dosing control error
0000 0000
bin
0010 0000
bin
: Release input stop
0000 0000
bin
0100 0000
bin
: Diaphragm rupture
0000 0000
bin
1000 0000
bin
: 0/4 - 20mA input error
0000 0001
bin
0000 0000
bin
: Manual stop
0000 0010
bin
0000 0000
bin
: General unit error
0000 0100
bin
0000 0000
bin
: Over temperature/overload
0000 1000
bin
0000 0000
bin
: Offline/transfer error
0001 0000
bin
0000 0000
bin
: RTC error/battery error
0010 0000
bin
0000 0000
bin
: Stroke buffer maximum
0100 0000
bin
0000 0000
bin
: Voltage error
Type
Description
Number
2 Bytes = 0000
hex
… FFFF
hex
= 0
dec
… 65536
dec
= 00000000
bin
… 11111111
bin
Text
2 Bytes = "aa"
ASCII
… "ZZ"
ASCII
Address
Word
r/w
Type
Field
Description
Table 17-1: Addresses of MODBUS TCP/IP protocol (MAGDOS LP-Net)
Parameter
Factory setting
Own setting
Language
English
Units
Litres/hr.
Alarm relay
Not active
Level input
Not active
Diaphragm rupture
Not active
Release input
Not active
Dosing control
Not active
Release code
Off
Safety code
Off
Eco-Mode
Off
IP address (MAGDOS LP-Net)
169.254.055.114
Analog input
0/4 … 0.20mA
4...20 mA
0%
4.0 mA
100%
20.00 mA
Table 17-2: Default settings
Содержание MAGDOS LP
Страница 2: ......
Страница 70: ...70 Solenoid Diaphragm Dosing Pump MAGDOS LP Lutz Jesco GmbH 2014 Operating Instructions BA 10231 02 V03 Notes ...
Страница 75: ......