Fixture Earth

Green/Yellow

Switched Line/Hot (Red)

Line/Hot (Black)

Neutral (White)

Neutral

Fixture/ 
Troffer or 
Junction  
Box

1/2 in (21 mm) 
Knockout 
Opening

From back of 
sensor

Emergency 

Driver / Ballast

Conduit Nut

N

L

Fixture Earth

Green/Yellow

Switched Line/Hot (Red)

Line/Hot (Black)

Neutral (White)

Neutral

Fixture/ 
Troffer or 
Junction  
Box

1/2 in (21 mm) 
Knockout 
Opening

From back of 
sensor

Normal 

Driver / Ballast

Conduit Nut

FCJS-010  
FCJS-010-EM
0 –10  V

-

FCJS-ECO 
FCJS-ECO-EM
Lutron EcoSystem

PowPak Wireless Fixture Control

 

UL 2043 Plenum Rated
UL 924 Listed (FCJS-010-EM / FCJS-ECO-EM)

Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or 
driver to limit the sink/source current draw to 2.0 mA maximum).  

Provides  IEC  SELV / NEC

R

 

Class 2, 12 V

-

, 25 mA to a PowPak

 

fixture sensor  

(FC-SENSOR or FC-VSENSOR).

Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA

Part of the Vive Family

PowPak Fixture Controls
Installation

Required Components 

For each fixture, you will need:

PowPak Fixture Sensor 
(FC-SENSOR or  
FC-VSENSOR)

(1 maximum)

Pico  
Remote Control

(10 maximum)

6 mA maximum for the control lines. Switches up to 1 A total (or 
maximum 3 ballasts or drivers). May be pre-installed in fixture.

Note:

 All drivers and ballasts used with Vive wireless controls must 

comply with the limits for a Class A device, pursuant to Part 15 of the 
FCC rules.

PowPak Wireless Fixture Control 
(FCJS-010 / FCJS-010-EM  or 
FCJS-ECO / FCJS-ECO-EM)

Raise

Toggle

Lower

Load 
Status 
LED

Consult the fixture installation guide for fixture wiring. 
For mounting and wiring best practices see Lutron Application Note #620 (P/N 048620).

 Start Here

English

Important Notes:

 

Please read before installing.

•  For installation by a qualified electrician in accordance with all local and 

national electrical codes (including periodic testing and maintenance of 
emergency systems).

•  Use copper conductors only.
•  Check to see that the device type and rating is suitable for the application.
• 

DO NOT

 install if product has any visible damage.

•  If moisture or condensation is evident, allow the product to dry completely 

before installation.

•  Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient.
•  0% to 90% humidity, non-condensing.
•  For indoor use only.

  120 – 277  V

~

  50 / 60 Hz  1 A switching

PIR Lens

Laser 
Detection

Daylight Lens

Radio Powr Savr

 

Occupancy/Vacancy 
Sensor

(10 maximum)

Radio Powr Savr

 

Daylight Sensor

(1 maximum)

6 mA sink/source 

Notes:

 

1.  Fixture control can be used 

without a fixture sensor as long 
as at least one Radio Powr 
Savr sensor or Pico remote 
control is  used.

2.  Only one fixture control can be 

used per fixture sensor, and 
only one fixture sensor can be 
used per fixture control.

Pico  
remote 
control

30 ft (9 m) 

maximum

PowPak  

Fixture Control 

Install the fixture control directly to  

a fixture or on a junction box nearest  

to the fixture. Install the sensor on the ceiling near 

the fixture to optimize coverage in the desired area.

Fixture 
Control 

Sensor

For more information please refer to Lutron P/N 369918 at 
www.lutron.com

 Notes:

1.  Control wires (Violet/Gray for FCJS-010 / FCJS-010-EM or 

Violet/Violet for FCJS-ECO / FCJS-ECO-EM) can be run as 
either Class 1 or Class 2.

2.  If hanging pendant fixtures the maximum wire length 

between fixture sensor and fixture control is 12 ft (3.7 m). 
Sensor should be mounted no more than 2 ft (0.6 m) from 
the fixture.

3.  To install unit inside a junction box, please see Lutron 

Application Note #423 (P/N 048423) on www.lutron.com

4.  When not using the Vive Hub, the fixture control needs to 

be accessible for some programming steps. Record where 
it is mounted so that it can be easily located later.

5.  When using a Radio Powr Savr daylight sensor in 

conjunction with both a PowPak wireless fixture control 
and PowPak fixture sensor, the Radio Powr Savr daylight 
sensor will provide the daylighting input to the control 
module, and the PowPak fixture sensor daylighting input 
will be ignored.

6.  When using a Radio Powr Savr occupancy sensor in 

conjunction with both a PowPak wireless fixture control 
and PowPak fixture sensor, occupancy data from both 
sensors is used; either one detecting occupancy will 
turn the lights on, and the lights turn off only when both 
sensors have gone vacant (no longer detect occupancy).

7.  For more information on the PowPak fixture sensor, see:  

P/N 369866 or P/N 048556 on www.lutron.com  
For FC-SENSOR and FC-VSENSOR installation guide visit  
www.lutron.com 

+

One Fixture Control 

At least one of these transmitters (22 total allowed) 

FCJS-010 / FCJS-010-EM:

 

At least one 0 –10 V

-

 Fluorescent Ballast or LED Driver

FCJS-ECO / FCJS-ECO-EM:

 

At least one Lutron EcoSystem Ballast or LED Driver

+

  120 – 277  V

~

  50 / 60 Hz  1 A switching

14 V

-

  6 mA

Note for Replacement:

FCJS - the "S" model can replace the non-"S" model

 Reset Factory Defaults

   Note:

 In some instances, it may be necessary to reset the fi xture 

controls and connected devices back to factory default settings. 
Before beginning, make sure that all devices are connected and 
powered.

A

  Rapidly tap the 

Toggle

 button “ 

u

”  on the fi xture control three 

times and hold on the fourth until the LED begins to flash slowly; 
release button.

B

  Within 3 seconds of the start of flashing, again rapidly tap the 

Toggle

 button “ 

u

”  three times and the LEDs will flash rapidly 

indicating that the unit has been reset to factory defaults.

   Note:

 Any associations or programming previously set up 

with the fi xture control will be erased and will need to be 
re-programmed.

Customer Assistance    www.lutron.com/support

041645 
Rev. A 
03/2018

  Install Fixture Control and Optional Fixture Sensor

 

Suggested Installation Location: Close to the Fixture / Troffer.

 

The fixture control can be installed on a fixture/troffer, junction box or marshalling box 
using the conduit nut (provided) or with mounting screws (not provided). Product must 
NOT be mounted inside a fixture - only on the exterior of a fixture. Please consult local 
and national electric codes for proper installation.

A

 

Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using 
the adhesive strip (included). The two communication wires from the sensor attach to the 
fixture control stab-in connectors. The wires are interchangeable to eliminate miswiring.  

Note:

 For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com

B

 

Once installed, energize the control module. The fixture will turn on.

WARNING! Shock Hazard.

 

May result in serious injury or death. 

Turn off power at circuit breaker before installing the unit.

1

Wireless sensors  
and controls must be  
located within 60 ft (18 m)  
line of sight, or 30 ft (9 m), through  
walls, of the associated control module. 

vive.lutron.com

X

Programming with a Vive Hub

2

 

Use an iOS

®

 or Android

®

  

compatible device.

 

C   

Open the app and follow the 
instructions.

 

  Note:

 For further information on set up, 

programming, and troubleshooting with a 
Vive system, please refer to the installation 
instructions included with the Vive hub or 
visit www.lutron.com/vive

 

  

Note:

 For programming the PowPak Fixture 

Control Module without a Vive hub see the 
reverse side.

X

Vive

 

Download the Lutron  
Vive app.

Emergency  
Backup Generator

Automatic  

Transfer  

Switch

Neutral 

120 / 277  V

~

   

Emergency Feed

Regular  
Utility Power

Neutral 

120 / 277  V

~

  Normal Feed

Neutral 

120 / 277 V

~

 Generator /

Emergency Feed

Important Note: 

To optimize RF performance of the product:  

–  Keep the lamp wiring as short as possible to reduce the 

radiation from the lamp wires.

–  Keep the lamp wiring as far as possible from the PowPak 

Wireless Fixture Control mounting location.

See the 

Troubleshooting

 section for more details.

Maximize Distance

PowPak Fixture 
Control Knockout

PowPak Fixture 
Control Wiring

Lamp 
Wiring

Note:

  For periodic testing and maintanance of emergency systems, use 

the toggle button of the FCJS-010-EM / FCJS-ECO-EM to ensure 
proper operation. Make sure PowPak buttons remain accessible. 

Note:

  Momentary power outages can envoke emergency mode on the 

fixture controller. See 

Troubleshooting

 section for details.

FCJS-010-EM /  
FCJS-ECO-EM only

FCJS-010: – (Gray), + (Violet)

FCJS-ECO: E1 (Violet), E2 (Violet)

FCJS-010-EM: – (Gray), + (Violet)

FCJS-ECO-EM: E1 (Violet), E2 (Violet)

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be  
followed including the following:

READ AND FOLLOW ALL SAFETY 
INSTRUCTIONS.

•  Do not use outdoors.
•  Do not mount near gas or electric heaters.
•  

Equipment should be mounted in locations and at heights where it will not be 
subjected to tampering by unauthorized personnel.

•  

The use of accessory equipment not recommended by the manufacturer may cause 
an unsafe condition.

•  Do not use this equipment for other than its intended use.