N
L
Fixture Earth
Green/Yellow
Switched Line/Hot (Red)
Line/Hot (Black)
Neutral (White)
Neutral
Fixture/
Troffer or
Junction
Box
1/2 in (21 mm)
Knockout
Opening
From back of
sensor
Emergency
Driver / Ballast
Conduit Nut
N
L
Fixture Earth
Green/Yellow
Switched Line/Hot (Red)
Line/Hot (Black)
Neutral (White)
Neutral
Fixture/
Troffer or
Junction
Box
1/2 in (21 mm)
Knockout
Opening
From back of
sensor
Normal
Driver / Ballast
Conduit Nut
FCJS-010
FCJS-010-EM
0 –10 V
-
FCJS-ECO
FCJS-ECO-EM
Lutron EcoSystem
PowPak Wireless Fixture Control
UL 2043 Plenum Rated
UL 924 Listed (FCJS-010-EM / FCJS-ECO-EM)
Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or
driver to limit the sink/source current draw to 2.0 mA maximum).
Provides IEC SELV / NEC
R
Class 2, 12 V
-
, 25 mA to a PowPak
fixture sensor
(FC-SENSOR or FC-VSENSOR).
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Part of the Vive Family
PowPak Fixture Controls
Installation
Required Components
For each fixture, you will need:
PowPak Fixture Sensor
(FC-SENSOR or
FC-VSENSOR)
(1 maximum)
Pico
Remote Control
(10 maximum)
6 mA maximum for the control lines. Switches up to 1 A total (or
maximum 3 ballasts or drivers). May be pre-installed in fixture.
Note:
All drivers and ballasts used with Vive wireless controls must
comply with the limits for a Class A device, pursuant to Part 15 of the
FCC rules.
PowPak Wireless Fixture Control
(FCJS-010 / FCJS-010-EM or
FCJS-ECO / FCJS-ECO-EM)
Raise
Toggle
Lower
Load
Status
LED
Consult the fixture installation guide for fixture wiring.
For mounting and wiring best practices see Lutron Application Note #620 (P/N 048620).
Start Here
English
Important Notes:
Please read before installing.
• For installation by a qualified electrician in accordance with all local and
national electrical codes (including periodic testing and maintenance of
emergency systems).
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
•
DO NOT
install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
120 – 277 V
~
50 / 60 Hz 1 A switching
PIR Lens
Laser
Detection
Daylight Lens
Radio Powr Savr
Occupancy/Vacancy
Sensor
(10 maximum)
Radio Powr Savr
Daylight Sensor
(1 maximum)
6 mA sink/source
Notes:
1. Fixture control can be used
without a fixture sensor as long
as at least one Radio Powr
Savr sensor or Pico remote
control is used.
2. Only one fixture control can be
used per fixture sensor, and
only one fixture sensor can be
used per fixture control.
Pico
remote
control
30 ft (9 m)
maximum
PowPak
Fixture Control
Install the fixture control directly to
a fixture or on a junction box nearest
to the fixture. Install the sensor on the ceiling near
the fixture to optimize coverage in the desired area.
Fixture
Control
Sensor
For more information please refer to Lutron P/N 369918 at
www.lutron.com
Notes:
1. Control wires (Violet/Gray for FCJS-010 / FCJS-010-EM or
Violet/Violet for FCJS-ECO / FCJS-ECO-EM) can be run as
either Class 1 or Class 2.
2. If hanging pendant fixtures the maximum wire length
between fixture sensor and fixture control is 12 ft (3.7 m).
Sensor should be mounted no more than 2 ft (0.6 m) from
the fixture.
3. To install unit inside a junction box, please see Lutron
Application Note #423 (P/N 048423) on www.lutron.com
4. When not using the Vive Hub, the fixture control needs to
be accessible for some programming steps. Record where
it is mounted so that it can be easily located later.
5. When using a Radio Powr Savr daylight sensor in
conjunction with both a PowPak wireless fixture control
and PowPak fixture sensor, the Radio Powr Savr daylight
sensor will provide the daylighting input to the control
module, and the PowPak fixture sensor daylighting input
will be ignored.
6. When using a Radio Powr Savr occupancy sensor in
conjunction with both a PowPak wireless fixture control
and PowPak fixture sensor, occupancy data from both
sensors is used; either one detecting occupancy will
turn the lights on, and the lights turn off only when both
sensors have gone vacant (no longer detect occupancy).
7. For more information on the PowPak fixture sensor, see:
P/N 369866 or P/N 048556 on www.lutron.com
For FC-SENSOR and FC-VSENSOR installation guide visit
www.lutron.com
+
One Fixture Control
At least one of these transmitters (22 total allowed)
FCJS-010 / FCJS-010-EM:
At least one 0 –10 V
-
Fluorescent Ballast or LED Driver
FCJS-ECO / FCJS-ECO-EM:
At least one Lutron EcoSystem Ballast or LED Driver
+
120 – 277 V
~
50 / 60 Hz 1 A switching
14 V
-
6 mA
Note for Replacement:
FCJS - the "S" model can replace the non-"S" model
Reset Factory Defaults
Note:
In some instances, it may be necessary to reset the fi xture
controls and connected devices back to factory default settings.
Before beginning, make sure that all devices are connected and
powered.
A
Rapidly tap the
Toggle
button “
u
” on the fi xture control three
times and hold on the fourth until the LED begins to flash slowly;
release button.
B
Within 3 seconds of the start of flashing, again rapidly tap the
Toggle
button “
u
” three times and the LEDs will flash rapidly
indicating that the unit has been reset to factory defaults.
Note:
Any associations or programming previously set up
with the fi xture control will be erased and will need to be
re-programmed.
Customer Assistance www.lutron.com/support
041645
Rev. A
03/2018
Install Fixture Control and Optional Fixture Sensor
Suggested Installation Location: Close to the Fixture / Troffer.
The fixture control can be installed on a fixture/troffer, junction box or marshalling box
using the conduit nut (provided) or with mounting screws (not provided). Product must
NOT be mounted inside a fixture - only on the exterior of a fixture. Please consult local
and national electric codes for proper installation.
A
Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using
the adhesive strip (included). The two communication wires from the sensor attach to the
fixture control stab-in connectors. The wires are interchangeable to eliminate miswiring.
Note:
For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com
B
Once installed, energize the control module. The fixture will turn on.
WARNING! Shock Hazard.
May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
1
Wireless sensors
and controls must be
located within 60 ft (18 m)
line of sight, or 30 ft (9 m), through
walls, of the associated control module.
vive.lutron.com
X
Programming with a Vive Hub
2
A
Use an iOS
®
or Android
®
compatible device.
C
Open the app and follow the
instructions.
Note:
For further information on set up,
programming, and troubleshooting with a
Vive system, please refer to the installation
instructions included with the Vive hub or
visit www.lutron.com/vive
Note:
For programming the PowPak Fixture
Control Module without a Vive hub see the
reverse side.
X
Vive
B
Download the Lutron
Vive app.
Emergency
Backup Generator
Automatic
Transfer
Switch
Neutral
120 / 277 V
~
Emergency Feed
Regular
Utility Power
Neutral
120 / 277 V
~
Normal Feed
Neutral
120 / 277 V
~
Generator /
Emergency Feed
Important Note:
To optimize RF performance of the product:
– Keep the lamp wiring as short as possible to reduce the
radiation from the lamp wires.
– Keep the lamp wiring as far as possible from the PowPak
Wireless Fixture Control mounting location.
See the
Troubleshooting
section for more details.
Maximize Distance
PowPak Fixture
Control Knockout
PowPak Fixture
Control Wiring
Lamp
Wiring
Note:
For periodic testing and maintanance of emergency systems, use
the toggle button of the FCJS-010-EM / FCJS-ECO-EM to ensure
proper operation. Make sure PowPak buttons remain accessible.
Note:
Momentary power outages can envoke emergency mode on the
fixture controller. See
Troubleshooting
section for details.
FCJS-010-EM /
FCJS-ECO-EM only
FCJS-010: – (Gray), + (Violet)
FCJS-ECO: E1 (Violet), E2 (Violet)
FCJS-010-EM: – (Gray), + (Violet)
FCJS-ECO-EM: E1 (Violet), E2 (Violet)
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS.
• Do not use outdoors.
• Do not mount near gas or electric heaters.
•
Equipment should be mounted in locations and at heights where it will not be
subjected to tampering by unauthorized personnel.
•
The use of accessory equipment not recommended by the manufacturer may cause
an unsafe condition.
• Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS