Lutron Electronics LUT-ELI-3PH Скачать руководство пользователя страница 8

EcoSystem

® 

Lighting Control Systems

Using a LUT-ELI-3PH unit with an 

EcoSystem

 bus supply ensures that the system is compliant with UL924. Follow the 

wiring diagram in the LUT-ELI-3PH unit instructions for main wiring. Use the diagram below to complete the installation. 

There can be up to 32 bus supplies connected to one LUT-ELI-3PH unit.

  Wiring Summary: 

•  Wire power pack red wire (+24 V) to LUT-ELI-3PH unit terminal 8 (+24VFW). 
•  Wire power pack black wire (Common) to LUT-ELI-3PH unit terminal 7 (Common) and to 

EcoSystem

 bus supply 

terminal 5 (Common).

•  Wire Signal wire from LUT-ELI-3PH unit (terminal 1) to 

EcoSystem

 bus supply terminal 6 (CCI-Emergency).

  Note:

 When normal power fails and the LUT-ELI-3PH unit trips, the 

EcoSystem

 bus supply stops powering the 

EcoSystem

 bus, and all ballasts will turn on to their emergency light level. 

  Note:

 The LUT-ELI-3PH unit includes 2 Fire Alarm Control Panel (FACP) inputs as well. Consult the LUT-ELI-3PH unit 

instructions for wiring details.

´FACP´ N/C

CONTACTS

´FACP´ N/O

CONTACTS

CLASS 2 LOW VOLTAGE WIRING

GND

SENSE

DRAIN

MUX

MUX

+24VFW

COMMON

NOT USED

LED1

LED3

LED2

RADIOTOUCH

PHASE

FACF

S1

TEST

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7

6

5

4

3

2

1

100-347 V  

normal 

supply

Common

Common

Neutral

Power

pack*

Hot

Common

(pin 5)

Emerg.

(terminal 6)

Connect up to 32

bus supplies

From Normal/

Emergency supply

bus supply

bus supply

24 V

Rasterized

24 V

Rasterized

100-277 V  

Normal/

Emergency 

supply

*PP-120H or PP-277H

S P E C I F I C AT I O N   S U b M I T TA L

Page

Job Name:

Job Number:

Model Numbers:

LUTRON

®

LUT-ELI-3PH

Power Accessories

P/N 369-299B    8   11.11.10                

8

Содержание LUT-ELI-3PH

Страница 1: ...nel circuit selector controller EcoSystem bus supply Energi Savr Node unit GRAFIK Eye QS system or Quantum bus supply with emergency essential power causing it to enter the emergency lighting mode Any...

Страница 2: ...ight Status light indicates the phase status Status light ON is normal mode OFF is emergency mode Test Button A test button is provided to perform a functional test of the system by simulating an emer...

Страница 3: ...FW COMMON NOT USED LED1 LED3 LED2 RADIOTOUCH PHASE FACF S1 TEST 2 50 in 63 5 mm 4 x 4 in 102 x 102 mm Junction Box For line voltage wiring only Mounting Example Side View Cross Section Insert NEC Clas...

Страница 4: ...3 Phase Diagram Single Phase Diagram Normal Power Normal Power Ground Neutral Hot Red Red White Green Guide to Power Source Wiring Red FACP N C CONTACTS FACP N O CONTACTS 12 11 10 9 8 7 6 5 4 3 2 1 CL...

Страница 5: ...Sense 1 18 AWG 1 0 mm2 5 Sense line To lighting controls NEC Class 2 PELV Wiring Example GRAFIK Systems GP XP and LP Panels One LUT ELI 3PH unit may be connected in parallel with up to 32 circuit sel...

Страница 6: ...Sense line Data Link 1 shielded twisted pair 18 AWG 1 0 mm2 3 MUX 4 MUX Control Wiring 2 12 AWG 2 5 mm2 1 Common 2 24 V Rasterized One LUT ELI 3PH unit may be connected in parallel with up to 32 LCP X...

Страница 7: ...onsulte la Gu a de Instaladores para informaci n m s detallada R f rer au Guide d installation pour plus de renseignements d taill s 120 277 V 60 Hz 16 A Max 0 10 V Red black Rojo Negro Rouge Noir Rad...

Страница 8: ...T ELI 3PH unit trips the EcoSystem bus supply stops powering the EcoSystem bus and all ballasts will turn on to their emergency light level Note The LUT ELI 3PH unit includes 2 Fire Alarm Control Pane...

Страница 9: ...it terminal 7 Circuit Common and to Energi Savr Node Com terminal of Emergency Contact Closure Input Wire Signal wire from LUT ELI 3PH unit terminal 1 to Energi Savr Node Emerg terminal of Emergency C...

Страница 10: ...ne LUT ELI 3PH unit Wiring Summary Wire power pack red wire 24 V to LUT ELI 3PH unit terminal 8 VFW Wire power pack black wire Common to LUT ELI 3PH unit terminal 7 Common and to Quantum bus supply te...

Страница 11: ...Unit FACP N O CONTACTS TAGE WIRING GND SENSE NOT USED LED1 LED3 LED2 RADIOTOUCH PHASE FACF S1 TEST 12 9 8 7 6 5 4 3 2 1 FACP CP N O C C ONTACTS TAGE WIRING SENSE NOT USED LED RADIOTOUCH 12 8 7 6 5 4 3...

Страница 12: ...ode Once the contact is released the LUT ELI 3PH unit will return the GRAFIK Systems GP LP XP panel s XPS LCP RadioTouch controller EcoSystem Bus Supply GRAFIK Eye QS unit or Quantum Bus Supply back t...

Отзывы: