EcoSystem
®
Lighting Control Systems
Using a LUT-ELI-3PH unit with an
EcoSystem
bus supply ensures that the system is compliant with UL924. Follow the
wiring diagram in the LUT-ELI-3PH unit instructions for main wiring. Use the diagram below to complete the installation.
There can be up to 32 bus supplies connected to one LUT-ELI-3PH unit.
Wiring Summary:
• Wire power pack red wire (+24 V) to LUT-ELI-3PH unit terminal 8 (+24VFW).
• Wire power pack black wire (Common) to LUT-ELI-3PH unit terminal 7 (Common) and to
EcoSystem
bus supply
terminal 5 (Common).
• Wire Signal wire from LUT-ELI-3PH unit (terminal 1) to
EcoSystem
bus supply terminal 6 (CCI-Emergency).
Note:
When normal power fails and the LUT-ELI-3PH unit trips, the
EcoSystem
bus supply stops powering the
EcoSystem
bus, and all ballasts will turn on to their emergency light level.
Note:
The LUT-ELI-3PH unit includes 2 Fire Alarm Control Panel (FACP) inputs as well. Consult the LUT-ELI-3PH unit
instructions for wiring details.
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
12
11
10
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
6
5
4
3
2
1
100-347 V
normal
supply
Common
Common
Neutral
Power
pack*
Hot
Common
(pin 5)
Emerg.
(terminal 6)
Connect up to 32
bus supplies
From Normal/
Emergency supply
bus supply
bus supply
24 V
Rasterized
24 V
Rasterized
100-277 V
Normal/
Emergency
supply
*PP-120H or PP-277H
S P E C I F I C AT I O N S U b M I T TA L
Page
Job Name:
Job Number:
Model Numbers:
LUTRON
®
LUT-ELI-3PH
Power Accessories
P/N 369-299B 8 11.11.10