´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12
11
10
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
6
5
4
3
2
1
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12
11
10
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
6
5
4
3
2
1
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
LUT-ELI-3PH Unit
Fire Alarm Control Panel
(provided by others)
Common
Normally
open
LUT-ELI-3PH Unit
Fire Alarm Control Panel
(provided by others)
Common
Normally
closed
Important
Use only with normally open (terminals 3 and
4) or normally closed (terminals 5 and 6) dry
contact closure. When the proper contact
state is triggered, it must be maintained for the
LUT-ELI-3PH unit to go into Emergency Mode.
Once the contact is released, the LUT-ELI-3PH
unit will return the GRAFIK
®
Systems GP, LP,
XP panel(s), XPS, LCP, RadioTouch
®
controller,
EcoSystem
®
bus Supply, GRAFIK Eye
®
QS
unit, or Quantum
®
bus Supply back to Normal
operation mode.
The LUT-ELI-3PH unit will have a factory
installed jumper to provide the normally closed
input signal for the supervisory circuit when a
normally closed FACP input is not provided.
Consult your Fire Alarm Control Panel’s
instruction manual before connecting to the
LUT-ELI-3PH unit.
NOTICE:
Do not connect any voltage source
to the FACP inputs on the LUT-ELI-3PH unit. If
voltage is provided by the FACP and connected
to the LUT-ELI-3PH unit, it can damage the
LUT-ELI-3PH unit.
NEC
®
Class 2/PELV Wiring Example:
Fire Alarm Control Panel (FACP)
Normally Open FACP Input
Supervisory Circuit (Normally Closed FACP Input)
To 24 V
Rasterized
power
To 24 V
Rasterized
power
S P E C I F I C AT I O N S U b M I T TA L
Page
Job Name:
Job Number:
Model Numbers:
LUTRON
®
LUT-ELI-3PH
Power Accessories
P/N 369-299B 12 11.11.10
12