LUT-ELI-3PH
Emergency Lighting Interface
Description
• The LUT-ELI-3PH unit is to be used in conjunction with
Lutron
GP, LP, LCP, XP, and XPS panels, RadioTouch
®
controllers, EcoSystem
®
bus supplies, Energi Savr
Node
TM
units, GRAFIK Eye
®
QS units, and Quantum
®
lighting management hubs.
• The LUT-ELI-3PH unit is UL924 Listed as “Emergency
Lighting and Power Equipment.”
• The LUT-ELI-3PH senses the normal (non-essential) line
voltage on all three phases of normal power. When one
or more phases of power are lost, the LUT-ELI-3PH unit
will send a signal to the
RadioTouch
controller, panel
circuit selector/controller,
EcoSystem
bus supply,
Energi
Savr Node
unit,
GRAFIK Eye
QS system or
Quantum
bus
supply with emergency (essential) power, causing it to
enter the emergency lighting mode. Any lights controlled
by these devices will go to the emergency light level
setting.
• When used with a
Energi Savr Node
unit,
EcoSystem
or
Quantum
bus supply, a separate 24 V
Rasterized
50 mA power
supply must be used to power the LUT-ELI-3PH unit.
Features
• Can be added to an existing system.
• Status indicator, indicates the phase status. Indicator ON
is normal mode, OFF is emergency mode.
• A test button is provided to perform a functional test of
the system by simulating an emergency situation.
• The interface has inputs for a Fire Alarm Control Panel
(FACP). A maintained dry contact closure received
between the FACP inputs will actuate the emergency
mode.
S P E C I F I C AT I O N S U b M I T TA L
Page
Job Name:
Job Number:
Model Numbers:
LUTRON
®
LUT-ELI-3PH
Power Accessories
P/N 369-299B 1 11.11.10
1