Installation Instructions
Occupant Copy
Allowable Wiring Configurations
Wiring/Installation
•
Refer to the system installation guide and Lutron job
drawings for power cable and data cable (control
link) wiring restrictions and limitations.
•
Connect the wallstation to the control link inside the
wallstation’s wallbox or in a junction box (provided
by others).
• Use the wire connector required by local code.
•
Control link wiring must
not
be run in the same
raceway as line voltage.
•
The drain/shield wire must be maintained throughout
the control link. Do
not
connect the shield to earth/
ground or allow contact with the grounded wallbox.
• Do not connect high-voltage power to low-
voltage ter mi nals. Improper wiring can result in
personal injury or damage to the control or to other
equipment.
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
Daisy chain
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
T-Tap
Warning! Shock hazard. May result
in serious injury or death.
Always turn
OFF the circuit breaker/MCB or remove
the main fuse from the power line before
doing any work.
1.
Turn Power OFF.
Turn
power OFF at circuit
breaker/MCB (or remove
fuse).
2.
Mount Wallbox.
Ensure correct size. See
“Mounting” for details.
3.
Prepare Wallstations.
Remove the faceplate and
set aside.
4.
Prepare wires.
Strip insulation from wires so that
4
in (10 mm) of bare wire is exposed.
ON
OFF
ON
OFF
ON
OFF
4
in (10 mm)
Wire Sizes (check compatibility in your area)
QS Link Wiring Length
Wire Gauge
Lutron Cable P/N
Less than 153 m (500 ft)
Power (terminals 1 and 2)
1 pair 1.0 mm
2
(18 AWG)
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
2
(22 AWG)
153 to 610 m
(500 to 2000 ft)
Power (terminals 1 and 2)
1 pair 4.0 mm
2
(12 AWG)
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
2
(22 AWG)
Wire Strip length