7
•
Meter Date
•
Meter Time
•
Meter Day of the Week
•
Tariff Intervals
•
Tariff Hours
•
Maximum Demand Period
•
Load Profile Period
•
Automatic Daylight Saving
Parameter
•
New Password
Other than the parameters above, none of the meter parameters can
be changed in any way.
1.7. RTC
RTC is in compliance with EN 61038 protocol. The maximum time
deviation is ±0.5 second daily.
1.8. Battery Operation
The meter operates with one main battery and optional secondary
battery. The battery / batteries provide necessary power supply in
case of absence of line power. Battery powered supply allows the me-
ter to be awaken with Menu Button in the absence of phase energy.
While the LCD is on, the meter data can be viewed on the LCD, or can
be read out using optical port.
The battery condition can be read by OBIS code “96.6.1”. The data in
the response from the meter is:
96.6.1(0) : battery is empty,
96.6.1(1) : battery level is OK.
1.9. Logs and Info
The meter keeps logs of the following information in its non-volatile
memory:
1.9.1. Phase Interruptions
The start and end-time of phase interruptions are stored in the non-vo-
latile memory of the meter. The meter records the date and time of
last 10 phase interruptions. The number of total phase interruptions
and the total phase-off duration can be read by OBIS code “96.7.1”
and 96.77.11 respectly, the date and time information of last 10
phase interruptions can be read by OBIS codes from “96.77.1*1” to
96.77.1*10”.
1.9.2. Phase Failure Notice
If there is no consumption record on any phase for 30 days, phase
failure message is received. For this failure 98.11 OBIS code is used.
1.9.3. Phase Active Energy Records
Total active energy consumed from ever phase is measured and re-
corded separately. This value is shown on the screen for every phase.
These values are hold by OBIS code and can be taken through the
optic port. OBIS codes used for these values:
For active power hold from L1 phase: 21.8.0
For active power hold from L2 phase: 41.8.0
For active power hold from L3 phase: 61.8.0
FK.104 (Rev.01) 19.10.2018