Luna LSM Series Скачать руководство пользователя страница 5

5

1. GENERAL FEATURES

1.1. Metrology

LSM Series Active-Reactive Electric Electricity Meters can measure 

and record active import energy. Voltage and current measurement, 

and energy calculation is carried out by the microprocessor in the me-

ter. If energy is in reverse direction, the import meter takes its absolute 

value and assumes it as positive. The import-export meter, however, 

measures and stores the data of import and export energy separately. 

Additionally, reactive energy can also be measured.

1.2. Software Version

Meter Software version can be readout from e-meter via OBIS code 

96.97.

1.3. Tariffs

1.3.1. Main Tariffs and Tariff Intervals

LSM  Series  Active-Reactive  Electric  Electricity  Meters  are  able  to 

split  day  time  as  import  and  export,  and  store  measurement  data 

for 4 tariffs and 8 billing periods for weekdays, Saturdays and Sun-

days  separately. The  measured  energy  is  added  to  both  total  tariff 

(T) and the corresponding tariff (T1, T2, T3 or T4). The tariff informa-

tion can be viewed on LCD or read out using the OBIS codes from 

1.8.0 to 1.8.4 (import) and from 2.8.0 to 2.8.4 (export**) in the format: 

(000000.000*kWh)
1.8.0 and 2.8.0 gives the total tariff (T) information and 1.8.1,... ,1.8.4 

and 2.8.1,..., 2.8.4 gives T1, T2, T3, T4 information of import energy 

and export energy respectively.
At  the  end  of  each  month, T, T1, T2, T3  and T4  data  is  automati-

cally stored in the non-volatile memory of the meter as the previous 

month’s record. Last 24 months’ data is always stored in the non-vo-

latile memory automatically. The previous months’ tariff data can be 

read  using  OBIS  codes  from  1.8.1*1  to  1.8.4*24  (import)  and  from 

2.8.1*1 to 2.8.4*24 (export**). For instance, 1.8.1*1 OBIS code cor-

responds to the previous month’s Import Tariff 1 record; the last 24 

month’s  Import  T1  parameter  can  be  read  with  OBIS  codes  from 

1.8.1*1 to 1.8.1*24.
Tariff intervals are pre-programmed as follows

 

Tariff 1: 06:00 - 17:00

 

Tariff 2: 17:00 - 22:00

 

Tariff 3: 22:00 - 06:00

 

Tariff 4: -

Automatic daylight saving is active by default. It can be disabled using 

the OBIS code 96.98(10) and re-enabled with 96.98(00).
In case extra intervals or tariff changes are needed, it can only be 

performed by authorized personnel using optical port interface.

1.3.2. Advanced Tariff (Optional)

LSM meters optionally have advanced tariffs structure. 8 different tariff 

FK.104 (Rev.01) 19.10.2018

Содержание LSM Series

Страница 1: ...IMPORT EXPORT ACTIVE REACTIVE SINGLE PHASE ELECTRONIC ELECTRICITY METERS MAINTENANCE AND USER S MANUAL LSM40 LSM SERIES KK_EN_LSM40_19 02...

Страница 2: ...Str No 9 Atat rk O S B 35620 i li zmir T RK YE Tel 90 232 472 15 45 Fax 90 232 472 15 50 www lunatr com SERVICES Main Technical Service LUNA ELEKTR K ELEKTRON K SAN VE T C A 10001 Str No 9 Atat rk O...

Страница 3: ...eatures in user s manual of LUNA Electronic Electricity Meters usage out of range set in the manual are not considered under cover of warranty LSM Series Active Reactive Multi Tariff Single Phase Elec...

Страница 4: ...the electricity distri bution company must be complied Humidity direct exposure to sunlight rain and cold should be avoided As electricity measurement are performed using electronic com ponents to avo...

Страница 5: ...rom 2 8 0 to 2 8 4 export in the format 000000 000 kWh 1 8 0 and 2 8 0 gives the total tariff T information and 1 8 1 1 8 4 and 2 8 1 2 8 4 gives T1 T2 T3 T4 information of import energy and export en...

Страница 6: ...s process is done automatically at the end of month if the maximum demand is not reset manually within that month LSM series meters stores the maximum demand and date and time of the maximum demand fo...

Страница 7: ...The meter keeps logs of the following information in its non volatile memory 1 9 1 Phase Interruptions The start and end time of phase interruptions are stored in the non vo latile memory of the mete...

Страница 8: ...n in this case unless the menu button is pressed and auto scrolling is off 1 9 7 Magnetic Interventions The last 10 intervals when magnetic field is applied and the number of magnetic interventions ar...

Страница 9: ...he poly phase meter is unbalanced with respect to the average current of all phases 1 at least one of the phase voltages in the poly phase meter is unbalanced with respect to the average voltage of al...

Страница 10: ...read with the LSM meter reading software using the Status tab After reading the statuses the bits which are set ap pear in bold on the left with their meanings Note that some of the status bits may n...

Страница 11: ...oad profile data is erased If export feature is enabled import and export consumptions are recorded however if export feature is disabled only the import consumption is recorded which significantly in...

Страница 12: ...connected if the feature is enabled If the Consumption Limitation Repeat 96 74 24 feature is enabled value 1 the electricity can be reconnected for Allowed Button Connect Count 96 73 33 times by pushi...

Страница 13: ...related to over and under voltage events that can be changed are as follows val_ov 96 73 20 The value of voltage over which over voltage is detected val_uv 96 73 21 The value of voltage below which u...

Страница 14: ...cannot reconnect the lr until the end of the month if this feature is enabled 1 10 16 Auto Disconnect LR on Over Current Consumption Limitation LSM Series meters can optionally support disconnecting...

Страница 15: ...YY MM DD hh mm A1 000000 OBIS code with data format where A is the password level 0 1 2 The complete writing logs can be read by asking the meter 96 92 X 00 OBIS code starting with X as 1 and incremen...

Страница 16: ...erations resets demand With this button the past month information about invoice periods can be gi ven Example 1 8 1 1 The OBIS value indicates the T1 consumption rate for the previous invoice period...

Страница 17: ...ve Reactive Model Each light pulse indicates 1 VArh reactive power consumption 2 5 Optical Port Optical port feature enables data transfer and programming in comp liance with EN 61107 communication pr...

Страница 18: ...on 2 Option 3 5 MENUS 5 1 Main Menu When the device is connected to energy the list indicating Total Im port Active Energy menu will appear in terms of kWh on the LCD scre en At 5 second intervals T1...

Страница 19: ...The menu is as records of the export energy used at the specified time in terval EXPORT T3 TARIFF The menu is as records of the export energy used at the specified time in terval EXPORT T4 TARIFF Menu...

Страница 20: ...case of unauthorized exe cution of this process warranty will be invalid and penalty fees may be incurred MAIN COVER REMOVAL NOTIFICATION It indicates that main cover is opened In case of unautho rize...

Страница 21: ...he menu but ton of the meter for 4 seconds In the sub menu Voltage Current Power Factor Frequency information and previous month information of T T1 T2 T3 T4 Reactive inductive Reactive Capacitive Dem...

Страница 22: ...umed energy T4 ta riff in previous month menu T4 blinks Total consumed energy Reacti ve Inductive in previous month menu Total consumed energy Reacti ve Capacitive in previous month menu Total demand...

Страница 23: ...SCHEME 7 CONNECTIONS FK 104 Rev 01 19 10 2018 6 SPHYSICAL DIMENSIONS OF THE METER Phase R Phase S Phase T Neutral LOAD LCD SCREEN MENU BUTTON OPTICAL PORR Demand Reset Button Optional Seal of Distribu...

Страница 24: ...vuzu 7 2 Say 5 OIML R 46 1 2 S r m 2012 E Direktif 2015 13 EU Directive 2014 32 EU of the European Par liament and of the Council of 26 February 2014 on the harmonisation of the laws of the member sta...

Страница 25: ...warranty cert f cate Customer Product Brand Type Model Name Name Address Address Tel Fax Tel Fax e mail Invoice Date Number e mail Serial Number LUNA APPROVAL Stamp Signature Electronic Electricity M...

Страница 26: ...ustrial product with similar features to the consumer until the completion of repair of the product 7 Failures resulting from the use contrary to the matters located in the user manual for the product...

Страница 27: ...ng Temperature Range T1 Tariff T2 Tariff T3 Tariff Daylight Saving Time Battery Life Weight LSM40 3 x 230 400VAC 20 Un 15 Un 5 100 A 1000 imp kWh 20mA 50 Hz 2 Directly connected to primary active reac...

Страница 28: ...ELECTRONIC ELECTRICITY METERS SMART GRID SYSTEMS Phone 90 232 472 15 45 Fax 90 232 472 15 50 info lunatr com www lunatr com...

Отзывы: