ROUTINE TEST RECORD

Type Test

Year 1

Year 2

Year 3

Year 4

Year 5

 

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Functional 1
Functional 2
Functional 3
Functional 4
Functional 5
Functional 6
Functional 7
Functional 8
Functional 9

Functional 10
Functional 11

3hr Duration 12

Installation Engineers Contact Details:

Luminaire Reference / Location

Name:

Tel:

Luminaire Details:

Full Recharge Duration 

24 Hours

Emergency Duration 

3 Hours

Lamp Type 

LED

Fontburn Emergency 2in1 Exit Sign

Emergency  0 to +30ºC

Technical Helpline: +44 (0)1507 328031

DISPOSAL

PRODUCT TEMP SPECIFICATION

FONTBURN EXIT SIGN DIMENSIONS

Part No. Description Watts L

 (mm)

W

 (mm)

H

 (mm)

Weight

421301

Exit Sign

3W

310

35

230 0.96Kg

421302

Exit Sign 

Self-Test

3W

310

35

230 0.96Kg

421304

Hanging

Exit Sign

3W

300

45

700 0.98Kg

421311

Hanging

Exit Sign

Self-Test

3W

300

45

700 0.98Kg

Revision 2.0 - May 2022

This luminaire is warranted for a 

period of 5 years from the date of 

purchase**.

 The backup battery  

pack in the emergency version 

is warranted for a period of 24 

months. The warranty could be 

invalidated should the light fitting 

not be installed according to these 

instructions, outside the scope of 

the specification or the product 

has been altered or tampered with 

in any way. Please see website for  

terms and conditions.  

WARRANTY

Disassembly instructions for end of 

life disposal available on website.
Disposal of Electronic Equipment 

WEEE Directive 2002/96/EC This 

product falls within the scope of 

the Waste Electrical & Electronic 

Equipment Directive (WEEE), which 

means the product should not be 

disposed of as normal household 

waste. Please recycle where  

facilities exist or check with your 

Local Authority.  RoHS – All  

components and materials used in 

this product are RoHS 2002/95/EC 

compliant.
Specifications may change from time 

to time. The information contained 

in this leaflet is for guidance only 

and should not be considered as  

always accurate and should be  

treated as not representative.

** Please see our website for more detailed information on warranty.

1.  Connect incoming earth cable to ‘Earth’ terminal on connector block.
2.  Connect incoming neutral cable to ‘Neutral’ terminal on connector block.
3.  For the emergency unit to work correctly, please ensure that an  

  uninterrupted permanent live feed is present and is connected directly  

  to the ‘Permanent Live’ terminal of the mains terminal block. Please  

  ensure there are no switches, PIRs etc within the permanent live feed, 

  constant switching of the emergency pack could result in premature 

  battery failure. 
4.  Connect incoming switched live cable to the terminal marked  

  “Switched Live”

NOTE: If there is no switch live feed and the unit has a microwave sensor, 

simply bridge across from the “Permanent Live” to the Switch Live” on the 

mains terminal block.

5.  There should be a loose flying lead connected to the battery. This needs  

  to be attached to the flying lead from the emergency control unit. 
6.  Following power up the green LED indicator should illuminate to indicate 

  charging. If power to the unit is disrupted or isolated, the unit indicating 

  green LED will switch off, triggering the emergency LEDs to illuminate.
7.  Please allow 24 hours charge before first emergency test.

The self-test version of emergency is fitted with control gear that will carry out  

periodic functional tests every 1 month and full duration test every 12 months. 

Wiring instructions for units equipped  

an with EMERGENCY function

Self-Test EMERGENCY function

Emergency lighting luminaries must be installed and maintained in 

accordance with the emergency lighting standard BS 5266-1

Fault/Test/Status

Reason

Battery fully charged  

and operational

Standard daily use

Battery Charging

Initial charge /  

battery topping up

Battery Failure

Battery is disconnected or 

damaged/faulty

Duration Test Failure

Maintenance check required  

by qualified engineer

Automatic Testing - Function  

5 minute test (Every 30 days)

Self-testing in  

operation

Automatic Testing -   

Duration test is 3 hours  

(every 12 months)

Self-testing in  

operation

Charge Indicator Status

Battery Fully Charged 

and Operational

Battery Charging

Auto Test 

5 Min

 

(every 30 days)

Auto Test 

3 Hours 

(every 12 months)

Duration Test Failure

1 Sec ON

1 Sec OFF

3 Sec ON

3 Sec OFF

3 Sec ON

1 Sec OFF

0.5 Sec ON

0.5 Sec OFF

Battery  

Disconnected/Faulty

This product contains a light source of energy efficiency Class G.

EMERGENCY FITTINGS ONLY. EARTH CONNECTION REQUIRED.

L   -  LIVE (SW)

 = Brown

N   -  NEUTRAL

 = Blue

L1  -  PERMANENT LIVE (PL)

 = Black

      -  EARTH 

= Green/Yellow

L (mm)

L (mm)

W (mm)

W (mm)

H (mm)

H (mm)