7.
Installation
These power supplies are designed for and intended only for installation into OEM pulse
forming systems.
Only qualified technicians or qualified assemblers may install these power
supplies.
Only qualified Lumina Power personnel may service these power supplies.
There are no user serviceable parts in this equipment.
Required wire and connectors
: Refer to Figure 3, CCPF-3500 Mechanical
Outline Drawing for the locations of connections. Table 2, CCPF Connections
below shows required cables and connectors:
Table 2, CCPF Connections
Connection
Description
Required Wire and Connectors
AC Input Power
2 Position terminal strip
#10-32 stud for ground
At least 12AWG wire
Interface
15 pin “D” female
15 pin “D” male
HV Output
TE/AMP LGH
receptacle
*See note below
LGH plug with coax cable rated for at
least 150% of maximum output
voltage of unit
24V Aux Output
(optional)
2 Pin Tyco Mate-N-Lok
Connector.
Tyco 35077-1 2 Pos Plug
(Digikey P/N A14279-ND)
Tyco 350550-1 Contacts
(Digikey P/N A1441-ND)
* Note: other connectors or flying lead configuration also available, contact
Lumina Power for any interface changes.
Ventilation:
This unit is forced air cooled via internal DC fans. A clearance of
2” should be maintained at either side of the power supply the fan end of the
power supply as well as the grill side of the power supply. Hot air exits the grill
side and should be ducted out of the system. Do not let the hot air exhaust
recirculate to the power supply air inlet. Fully sealed systems should implement a
heat exchanger system to maintain the environmental conditions list in section 3
CCPF-3500/4000-XX Specifications on page 5.
IMPORTANT APPLICATON NOTE REGARDING AC INPUT POWER
AC Input wires should be at least #12 AWG,
rated for at least 600V and 105 Degree C.