23
Note that, ...
...the data required to perform the electrical insulation
task agree with the data on the nameplate of the
Isolator ( input E,
output A1 & A2 and
power supply H !)
...the total loop resistance connected to the output
(receiver plus leads) does not exceed the maximum
permissible value R max. See “Measuring Output” in
ext
sec. “6. Technical data” for the maximum values of
R !
ext
...the input and output cables should be twisted pairs
and run as far as possible away from heavy current
cables !
In all other respects, observe all local regulations
when selecting the type of electrical cable and
installing them !
Make sure that the cables are not live
when making the connections !
Input connections are made directly to screw-type terminals with
indirect wire pressure. Choice of cable should meet local regulations.
Terminal for Current
2
.
5
mm² single wire
.
inputs will accept up to <
7. Electrical connections