3. FUNCTION DESCRIPTION
In the R15 controller following protocol functions have been
implemented:
Code
Signification
03
Reading of n-register
06
Writing of an individual register
16
Writing of n-registers
17
Slave device identification
3.1. Reading of n-registers (code 03)
Demand:
The function enables the reading of values included in registers in
being addressed slave device.
Registers are 16 or 32-bit units,
which can include numerical values bounded with
changeable processes, and the like
. The demand frame
defines the 16-bit start address and the number of registers to
read-out.
The maximal number of registers read out by one command is 128
for the RE15 controller.
The signification of the register contents with address data can be
different for different device types. The function is not accessible in
the broadcast mode.
The function is not accessible in the broadcasting mode.
Example:
Reading of 3 registers beginning by the register with the
6Bh address.
Address Funtion
Register
Register
Number of
Number of
Checksum
Address Hi
Address Lo
registers Hi
registers Lo
11
03
00
6B
00
03
7E
LRC