NA6Plus-09
25
User’s Manual
Request:
Device
address
Fun
ction
Register
address
Number of
registers
Number of
bytes
Value from register
1DBD h (7613)
Value from register
1DBE h (7614)
Checksum
CRC
Hi
Lo
Hi
Lo
01
10
1D BD 00
02
08
3F
80
00
00
40
00
00
00
03 09
Response:
Device
address
Function
Register address
Hi
Register
address Lo
Number of
registers Hi
Number of
registers Lo
Checksum
CRC
01
10
1D
BD
00
02
D7 80
Device identification (code 11 h)
Example
. Readout of data identifying a device for NA6Plus meter
Request:
Device
address
Function
Checksum CRC
01
11
C0 2C
Response:
Device
address
Function Number
of bytes
Device ID
State of the device
Field depending
on device type
Checksum
CRC
01
11
19
E1
FF
xxxxxxxxxxx
Device address
- depending on the setpoint
Function
- function no. (11 h)
Number of bytes
- 19 h
Device ID
- E1 h
Device state
- FF h
Field depending on device type
- device name
- software version
6.4 Map of NA6Plus meter registers
Address
range
Value type
Description
7000
float (32 bits)
Value is placed in two successive 16-bit registers. Registers
contain the same data as 32-bit registers of 7500 range.
Registers are read-only.
7100
float (32 bits)
Value is placed in two successive 16-bit registers. Registers
contain the same data as 32-bit registers of 7700 range.
Registers can be read out and recorded.
7200
float (32 bits)
Value is placed in two successive 16-bit registers. Registers
contain the same data as 32-bit registers of 7600 range.
Registers can be recorded and read out.
7320
float (32 bits)
Value is placed in two successive 16-bit registers. Registers
contain the same data as 32-bit registers of 7660 range.
Registers can be read out and recorded or only recorded.
7500
float (32 bits)
Value is placed in 32-bit register. Registers are read-only.
7600
float (32 bits)
Value is placed in 32-bit register. Registers can be recorded
and read out.