9. EXAMPLES OF NA5 METER PROGRAMMING
Example 1. Programming of the individual characteristic
.
If we want to programme so that to the value 4.00 mA will correspond the value 0
on the display, whereas the value 100, to the value 20.00 mA, one must:
l
enter into the programming mode and choose the
D_ P
parameter
responsible for the decimal point. Set the decimal point on
00000
l
choose the
Ind
parameter and switch the individual characteristic
On
l
choose the
I_H1
parameter and introduce the value 4.00
l
transit on the
d_Y1
parameter and introduce the value 0
l
transit on the
I_H2
parameter and introduce the value 20.00
l
transit on the
d_Y2
parameter and introduce the value 100
Example 2 Programming of an inverse individual characteristic
.
If we want to programme so that to the value 4.00 mA will correspond the value
120.5 on the display, and the value 10.8, to the value 20.00 mA, one must:
l
enter into the programming mode and choose the
D_P
parameter responsible
for the decimal point. Set the decimal point on
0000.0
l
choose the
Ind
parameter and switch the individual characteristic
On
l
choose the
I_H1
parameter and introduce the value 4.00
l
transit on the
d_Y1
parameter and introduce the value 120.5
l
transit on the
I_H2
parameter and introduce the value 20.00
l
transit on the
d_Y2
parameter and introduce the value 10.8
Example 3 Programming of the alarm with hysteresis
If we want to programme the alarm 1 operation so that at the value 850
°
C, this
alarm will be switched on, whereas it will be switched off at the value 100
°
C, and
the alarm 2 operation so that at the value 1000
°
C this alarm will be switched off
and switched on at the value -199
°
C, one must:
l
enter into the programming mode, choose the
PrL
parameter of the alarm 1
and introduce the value 100
l
transit on the
PrH
parameter of the alarm 1 and introduce the value 850
l
transit on the
tYPA
parameter of the alarm 1 and choose select the function
assigned as
nor
l
enter into the programming mode and choose the
PrL
parameter of the
alarm 2 and introduce the value 1000
l
transit on the
PrH
parameter of the alarm 2 and introduce the value -199
l
transit on the
tYPA
parameter of the alarm 2 and select the function
nor
All manuals and user guides at all-guides.com
Содержание NA5 Series
Страница 2: ...All manuals and user guides at all guides com...
Страница 4: ...All manuals and user guides at all guides com...
Страница 61: ...All manuals and user guides at all guides com a l l g u i d e s c o m...
Страница 62: ...All manuals and user guides at all guides com...
Страница 63: ...All manuals and user guides at all guides com...