Read-out of n-registers (code 03 h)
Function is inaccessible in the publication mode.
Example:
readout of 2 registers beginning from the register with the address
1 DBDh (7613) in RTU mode.
52 43
Device
address
Check-
sum
CRC
Function
Register
address
Hi
01
03
1D
BD
00
Register
address
Lo
Number of
registers
Hi
Number of
registers
Lo
02
Request:
Response:
42 8B
Device
address
Check-
sum
CRC
Function
Number
of bytes
01
03
08
Value from the register
1DBD (7613)
40
Value from the register
1DBE (7614)
00
00
00
00
00
80
3F
Record of values into the register (code 06h)
The function is accessible in the publication mode.
Example:
record of the register of 1DBDh (7613) address in RTU mode.
Request:
85 AD
Device
address
Check-
sum
CRC
Function
Register
address
Hi
01
06
1D
BD
3F
Register
address
Lo
00
80
00
Value from the register
1DBD (7613)
Response:
85 AD
Device
address
Check-
sum
CRC
Function
Register
address
Hi
01
06
1D
BD
3F
Register
address
Lo
00
80
00
Value from the register
1DBD (7613)
Record into n-registers (code 10h)
The function is accessible in the publication mode
Example:
record of two registers beginning from the register with
1DBDh (7613) address in RTU mode.
Request:
03 09
Device
address
Check-
sum
CRC
Function
Number
of bytes
01
10
BD
Value for the register
1DBD (7613)
40
Value for the register
1DBE (7614)
00 00 00
00
00
80
3F
Hi
1D
Lo
Hi
Lo
00
02
08
Register
address
Number of
registers
All manuals and user guides at all-guides.com
Содержание NA5 Series
Страница 2: ...All manuals and user guides at all guides com...
Страница 4: ...All manuals and user guides at all guides com...
Страница 61: ...All manuals and user guides at all guides com a l l g u i d e s c o m...
Страница 62: ...All manuals and user guides at all guides com...
Страница 63: ...All manuals and user guides at all guides com...