7.4 Setup for installation
Figure 18: Installation on basement
SR
™
horizontal air flow models with forced draught fans (FD)
You can install the horizontal air flow models directly. Remove the lifting lugs.
SR
™
vertical air flow models with forced draught fans (FD)
When mounting a vertical air flow unit, install the legs in the correct height. If you install the unit directly on a
plane surface, the height of the legs from the surface to the lower point of the fan collar is ca 550 mm. Install
also the horizontal supports for the legs. See
Figure 19: FD-model installation with legs
on page 46.
When you install the unit on a basement, you can install the legs in a steady middle position (ca 350 mm),
without the horizontal supports. When drawing air from only one side, the minimum height is 1100 mm. See
Figure 20: FD-model installation on open basement
on page 47.
Figure 19: FD-model installation with legs
©
Alfa LU-VE, Rev-04
46