5.2 Drain line
The drain line diameter must be at least the size
of the driptray drain diameter and should be laid
with an adequate slope. For room temperatures
below 0° C drain line insulation and defrosting
are required.
A syphon must be installed on the drain line,
outside the cold room.
Tighten drain connection by hand only.
5.3 Refrigerant connections
Never bend the air cooler refrigerant connection
tubes. Bends in refrigerant pipework are only
allowed in the external piping section.
For both CS200 and CS300 there is sufficient
space for mounting the expansion valve inside
the cooler casing. Casing cutaways available on
all cooler sides for refrigerant piping.
CS200
CS300
Expansion valve
Expansion valve