Installation/Use/Maintenance Instructions
Fan coil units VFC, installation in sills
E
LTG Incorporated · PO Box 2889 · Spartanburg, S.C. 29304, USA
VFC_USA_BA (07/19)
Phone 864 599-6340, Fax -6344 · e-mail: [email protected] · Internet: www.LTG-INC.net
Former editions are invalid · Subject to technical modifications
page 39 of 19
Continuation 5.2.1 Instructions for installation of water connections using flexible hoses
LTG Quick-Connection
O-Ring EPDM
Polysulfone ring
Inner ring
Outer ring of copper
Stainless steel retaining ring
Quick connection for copper tube or suitable brass or red
brass.
Components used meet KTW (Plastics in Drinking Water)
recommendations.
The Cuprofit plug-in connection has been evaluated based
on DVGW (German Association of the Gas and Water In
dustries) Worksheet W534, in connection with the use of
Wieland copper tubing. This permanently tight connection
is suitable for concealed installation.
Using the special quick connect tool, this connection may
be detached up to three times when not under pressure.
Prior to reconnection, check for loosened undamaged
condition of the seal.
Check after each installation to ensure the connection is
done properly.
Due to their specific design, quick connectors are not suit
able for use as grounding conductors for electrical instal
lations and therefore not to be considered in the compen
sation of potential.
Maximum operating pressure 145 psi / 200 °F
Test pressure
232 psi / 86 °F