A

Building Safety. Building Security.

•   ADM loop technology with

System Sensor/200 protocol

•   Up to 99 automatic detectors and 98 

manual call points can be controlled

•  Multi-language operating menu
•  High range of radio transmission
•   Two frequency bands (868/434MHz) 

with automatic change-over

•  Channel checked for availability

Description

Specifi cations

Operating voltage 

10 – 30VDC

Current consumption external supply (at 24V) 

max. 80mA

Current consumption from loop 

325µA (quiescent)

Range of radio transmission (free air) 

300m

Frequency band 

868MHz or 434MHz

Ambient temperature 

-10°C to +55°C

Dimensions W × H × D 

210 × 270 × 70 (mm)

Colour 

white/black

Weight 

930g

Approval 

VdS G208132

Order number 

249202

Order name 

RF Interface/Anal./SS M500RFE-AS

The  RF  Interface  M500RFE-AS  serves  as  a  gateway 

between radio detectors and a Fire Detection Control 

Panel Series BC216. The communication with the con-

trol panel is established via the ADM loop with System 

Sensor/200 protocol.

The RF interface can communicate with up to 99 auto-

matic radio detectors and up to 98 manual radio call 

points. For each automatic radio detector one detector 

is parameterised in the fi re detection control panel, and 

for  each  manual  radio  call  point  one  module  is  para-

meterised.  The  gateway  itself  occupies  one  module 

address on the loop.

The  detectors  are  confi gured  at  the  RF  interface  by 

means of the automatic learning process. A manual pa-

rameterisation is also possible.

The  RF  interface  is  operated  and  confi gured  using 

the built-in key pad and the alphanumeric display. The 

multi-language operating menu serves for the parame-

terisation as well as for displaying the signal strength 

of any individual detector. A 6-digit authorisation code 

provides protection against unauthorised access. Three 

LEDs indicate the interface conditions operation, alarm 

and fault.

The RF interface is designed for indoor surface moun-

ting and is equipped with a dual-isolator, which discon-

nects the loop in case of a short circuit.