Specifi cations
Mains voltage
10/-20%, 47...63Hz
Output/nominal voltage
typ. 27.6VDC
Output current
max. 2.2A
Output current siren outputs
output 1
max. 1A
output 2
max. 0.5A
(the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)
Output current, extinguishing output
max. 1A
Output current, activated condition output/signal output
max. 500mA per output
Own current consumption (incl. extinguishing board) at 24V
typ. 80mA (without optional componentries, line termination 5.6k
Ω
)
typ. 65mA (without optional componentries, line termination 47µF)
Line voltage
typ. 20V (line termination 5.6k
Ω
)
typ. 23V (line termination 47µF)
Line current without fi re detectors
typ. 3.7mA (line termination 5.6k
Ω
)
typ. 0mA (line termination 47µF)
Line termination
5.6k
Ω
or 47µF
Line resistance
max. 50
Ω
per core
Ambient temperature
-5°C to +50°C
Relative humidity
max. 95% (no condensation)
Dimensions W × H × D
330 × 330 × 90 (mm)
Colour
grey-white, RAL 9002
Weight without batteries
approx. 3kg
Approvals
0786-CPD-20300
VdS pending
Fire Detection Control Panel BC06-1EXT
Order number
210223
Order name
Fire Detection Control Panel BC06-1EXT/INT1
Fire Detection Control Panel BC06-2EXT
Order number
210224
Order name
Fire Detection Control Panel BC06-2EXT/INT1
Functions of EN 12094-1
All mandatory functions of EN 12094-1 are integrated
into the Fire/Extinguishing Control Panels BC06-1EXT
and BC06-2EXT. Furthermore, the most important opti-
onal functions of this standard are supported:
• Parameterisable pre-discharge-warning time for the
delay of the activation
• Detector zone „extinguishing medium active“ se-
lectable for detecting the fl ow of the extinguishing
medium
• Monitoring of components of the extinguishing sys-
tem
• Input for connection of an emergency hold device
• Monitoring of a disable device
• Parameterisable fl ooding time
• Possibility to switch to the „manual only mode“
• Transmission of the triggering signal to further actu-
ations within the extinguishing system – for example,
warning devices
• Transmission of the triggering signal to further actua-
tions outside the extinguishing system – for example,
for turning off the air conditioning system
• Emergency abort device can be connected
• Activation of alarming devices with different alarm
signals