© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
45681-290_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The Integrated Base Sounders 45681-277, 45681-290
and 45681-300 are fi tted into a round, white plastic
case with an integrated base for accommodating au-
tomatic Fire Detectors or Strobes Series XP95 or Dis-
covery.
The sounders are powered and actuated as modules via
the ADM loop with Apollo/Discovery protocol. They can
be used in combination with a detector or strobe, or as
stand-alone device. For the latter case an optional white
or red plastic lid is available. Furthermore, the sounders
are equipped with an integrated dual-isolator module.
Two different tone types, depending on the sounder
model, are available, and they can be selected during
parameterisation of the Fire Detection Control Panel Se-
ries BC216. If several sounders are actuated in parallel,
they are synchronized by Fire Detection Control Panels
Series BC216 to generate a uniform warning tone.
In case of activation, the sounder is tested acoustically
by means of an integrated microphone.
The address of the sounder as well as the sound level
are selected by means of a DIL switch.
The base sounders have been designed for indoor
mounting. An optional mounting plate is available for
surface mounted cabling.
• ADM loop technology with
Apollo/Discovery protocol
• Integrated detector base with
dual-isolator
• Warning tone 1kHz
• Slow whoop tone – NEN 2575
• Emergency signal tone – DIN 33404
• Sound level selectable in two steps–
up to 91dB(A)
• Integrated acoustical self test
Specifi cations
Operating voltage
17 – 28VDC
Current consumption
max. 200µA (sounder off)
max. 5mA (sounder on)
Sound level
55 – 75dB(A) or
75 – 91dB(A)
Ambient temperature
-20°C to +60°C
Dimensions ø × H
115 × 38 (mm)
Colour
white
Weight
140g