Operating voltage  

Supply through loop voltage

Current consumption  

typ. 250µA (quiescent)

Alarm temperature 

57°C (maximum-heat component)

Operating temperature 

max. +45°C

Ambient temperature 

-20°C to +60°C (no condensation or icing)

Relative humidity 

10 – 93% (no condensation)

Dimensions ø × H 

102 × 45 (mm)

Colour 

cream

Weight 

115g

Approvals 

VdS G201041

At operation in thermal-only mode: 

     EN 54-5 Class A1R 

57°C maximum and rate-of-rise activation

     Room height 

max. 7.5m

Order number 

241020

Order name 

Optical-Thermal Detector/Anal./200/SS 2251TEM