4. Error Code List
44
Object
Error code
Occurrence
location
Error message
Reason and measure
Type
Address
Project
download
0x26
0x15
XGT Panel
Failed to initialize
LOGGING area in
NV-RAM. Please
download project
again.
When downloading, the log data area in
the NV-RAM is initialized in case of
selecting previous project’s the monitor
data deletion option. By the way, in case
of failing this, downloading is stopped. If
this problem is repeated, contact
Customer Service Center.
0x16
XGT Panel
Failed to initialize
RECIPE area in NV-
RAM. Please
download project
again.
When downloading, the alarm history in
the NV-RAM is initialized in case of
selecting the previous project’s monitor
data deletion option. By the way, in case
of failing this, downloading is stopped. If
this problem is repeated, contact
Customer Service Center.
0x17
XGT Panel
Failed to initialize
ALARM area in NV-
RAM. Please
download project
again.
The downloaded font file is moved into
original storage location but when this
fails, downloading is stopped. If this
symptom is repeated, contact Customer
Service Center.
0x18
XGT Panel
Failed to install font
files. Please
download project
again.
The project data is divided into several
files according to the contents but when
this fails, downloading is stopped. If this
symptom is repeated, contact Customer
Service Center.
0x19
XGT Panel
Failed to unmarshall
download file.
Please download
project again.
The data divided according to the
contents is moved to the original storage
location but when this fails, downloading
is stopped. If this symptom is repeated,
contact Customer Service Center.
0x1A
XGT Panel
Failed to install new
project data files.
Please download
project again.
The downloaded project is not installed
normally because of error of the Flash
Disk. Download the project again. If this
symptom is repeated, contact Customer
Service Center.
0x1B
XGT Panel
Failed to merge data
files. Please
download project
again.
The downloaded project zip file is moved
tothe original storage location but when it
fails, downloading is stopped. If this
symptom is repeated, contact Customer
Service Center.
0x1C
XGT Panel
Failed to save new
project archive.
Please download
project again.
There is a program to reboot engine
program after downloading in the device
but when it fails, this message shows up.
But because the downloading is
completed if you reboot engine directly, it
works normally. The program name to
reboot is startup.exe and it can be
installed by engine upgrade function.
0x1D
XGT Panel
Failed to XGP Panel
startup program.
Please update XGT
Panel Software.
It can’t find software to reboot XGT
Panel. Update the XGT Panel.