
7-16
Note that setting Frequency Ref. for Accel/decel (H70) is set to Max Freq and target freq is set
below Max freq. the shape of S-curve may be distorted.
Accel time for S-curve setting
2
18
2
17
H
ACC
H
ACC
ACC
Decel time for S-curve setting
2
18
2
17
H
dEC
H
dEC
dEC
ACC, dEC indicate the set time in Drive group.
Accel/Decel Disable
Group
Code
Parameter Name
Setting
Range
Initial
Unit
I/O group
I17
[Multi-function input terminal
P1 define]
-
0 ~27
0
~
~
I24
[Multi-function input
terminal P8 define]
24
7
Select one terminal among Multi-function input terminals 1-8 to define Accel/Decel disable.
If P8 is selected, set I24 to 24 to activate this function.
CAUTION
If Target Frequency is
below Max Frequency, the
waveform will be shown
with the top portion cut out.
Freq
H17
H17
H18
H18
Accel/decel
Ref Freq
(H70)
Target Freq
Freq.
P8
Operating
command
For Service Call
800-848-2504
For Service Call
800-848-2504
Содержание sv-ig5a
Страница 10: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Страница 14: ...1 4 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Страница 28: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Страница 47: ...4 19 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Страница 48: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Страница 74: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Страница 80: ...6 6 Notes For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Страница 184: ...v For Service Call 800 848 2504 For Service Call 800 848 2504 ...
Страница 185: ...For Service Call 800 848 2504 For Service Call 800 848 2504 ...