Ratings - High Ambient Models
MODEL
Leaving
Chilled
Liquid
˚C
Condenser Air Entering Temperature
˚C
25
30
35
40
46
50
cool
Power
cool
Power
cool
Power
cool
Power
cool
Power
cool
Power
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
SA075
5
299
69
297
74
272
78
262
83
252
107
232
112
7
319
72
308
77
290
81
280
86
263
116
250
116
10
339
76
332
80
320
85
309
90
289
117
278
121
12
348
78
334
83
328
88
317
93
306
120
295
125
15
357
80
344
86
335
92
322
96
311
125
309
130
SA100
5
392
93
385
99
375
105
362
111
332
137
309
143
7
409
97
392
109
380
119
367
145
345
150
332
148
10
421
102
403
112
391
125
376
150
353
152
349
156
12
439
105
420
115
406
138
388
153
376
154
382
161
15
450
109
439
120
423
142
398
156
388
161
393
167
SA125
5
496
111
475
119
451
126
435
372
422
162
393
168
7
529
116
507
124
481
131
465
398
443
194
423
175
10
578
122
557
129
531
138
513
440
491
206
470
183
12
612
126
590
134
561
142
543
465
519
212
499
190
15
661
131
636
139
606
148
586
502
560
219
539
197
SA150
5
622
152
596
162
566
172
545
182
492
214
458
199
7
662
158
636
168
603
178
582
188
520
226
492
206
10
725
166
698
177
664
188
642
198
582
233
547
217
12
767
172
739
183
702
194
680
205
616
240
581
224
15
827
178
797
189
759
202
733
213
665
249
627
233
SA170
5
689
185
660
197
662
208
604
206
579
264
539
275
7
704
192
675
204
645
216
626
213
608
274
579
285
10
724
202
694
214
677
227
642
224
626
287
644
300
12
750
208
719
221
692
235
684
231
645
297
684
310
15
788
216
733
229
728
245
704
241
663
310
738
322
SA210
5
758
202
790
215
710
228
692
239
666
296
614
309
7
778
210
743
223
730
237
702
248
689
307
667
320
10
801
221
776
235
741
249
721
260
709
323
701
336
12
817
228
799
243
782
258
751
269
735
334
727
348
15
997
237
956
252
907
268
773
280
842
346
840
362
Note
:
1. High ambient models are suitable for operation in ambient temperatures up to 52˚c (125˚F)
2. Fouling factor of evaporator is 0.086 m2.·k/kW.
3. Specification may be changed without further notification
4. The unit conforms to standard ARI 550/590-98.
5. The cooling capacity and power supply is measured with the economizer.
6. Power consumption values include compressors and fans.
LS