14
Address
Parameter
Unit
R/W
Data value
BIT 2 M3
BIT 3 M4
BIT 4 M5
BIT 5 M6
BIT 6 M7
BIT 7 M8
BIT 8 P4
BIT 9 P5
BIT 10 P6
BIT11~15 Not Used
BIT 0 AUX1
BIT 1 AUX2
BIT 2 AUX3
BIT 3 AUX4
BIT 4 Q1 (OC1)
BIT 5 Q2 (OC2)
BIT 6 Q3 (OC3)
BIT 7 30AC
0x0010
Output Terminal
Information
- R
BIT 8~15 Not used
0x0012 V1
-
R
0 ~FFC0
0x0013 V2
-
R
0 ~FFC0
0x0014 I
-
R
0 ~FFC0
0x0015 RPM
- R
0x001A
Unit display
-
R 0 : Hz, 1 : Rpm
0x001B
Pole number
-
R
0x001C Custom Version
-
R
※
Refer to the main manual for the communication address regarding iP5A Function
Code.
7.1.2 iP5A Communication Option Setting
< COM Group >
Address
NO.
Description
Default
Maximum
Minimum
9601 COM-01 Opt B/D
0
7
0
9602 COM-02 Opt mode
0
3
0
9603 COM-03 Opt Version
0022h: Ver 2.2
-
-
963C COM-60 Parity/Stop
0
3
0
* Inverter Number or communication speed is set in I/O-90, 91.
COM-01 [Opt B/D]
z
Indicates the type of the option card installed.
z
This value is automatically displayed when the option card is installed.
COM-02 [Opt Mode]
z
Determines whether Run/Stop and Freq. command are set via communication.
Setting
Display
Description
0 None
None command
1 Command
Run/Stop command via communication