![LS RS485/Modbus-RTU Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/ls/rs485-modbus-rtu/rs485-modbus-rtu_user-manual_1943744012.webp)
11
0x06
Preset Single Register
0x10
Preset Multiple Register
5.2.2. Exception code
Exception code
Description
0x01
ILLEGAL FUNCTION
0x02
ILLEGAL DATA ADDRESS
0x03
ILLEGAL DATA VALUE
0x06
SLAVE DEVICE BUSY
User
define
0x14
1. Write Disable (Address 0x0004 value is 0).
2. Read Only or Not Program during Running.
5.3.
5.4.
6.
Baud Rate
1200, 2400, 4800, 9600, 19200, 38400 bps (Default value: 9600bps)
Broadcast Function
z
The broadcast function is used when Command is given to all inverters connected to network.
z
In the case of RS485, all inverters run without response (Slave->Master) when Command is given
to Inverter Number 255(0xFF).
z
In the case of Modbus-RTU, all inverters run without response (Slave->Master) when Command is
given to Inverter Number 0(0x00).
TROUBLE
SHOOTING
Refer to this chapter when occurring problem in communication with computer while using this option
card.
z
CPU LED malfunction
Expected
State
The inverter is not working normally or the inverter and the option card are not
connected properly.
Corrective
Measures
1. Verify the power is applied to the inverter.
2. Verify the option card is installed properly within the inverter when the inverter
is working normally.
z
RXD and TXD LEDs malfunction
Check Points
Corrective Measures
Is the power applied to the converter?
Apply power to the converter.
Is the connection between the converter and computer correct?
Refer to the converter manual
Is the communication card installed within the inverter properly? Refer to “4 Installation”.
Does Master start the communication?
Start the communication.
Is the communication speed setting of the inverter correct?
Refer to “4 Installation”.
Is the data format of User program correct?
Modify User program
note4).
Is the connection between the converter and the option card
correct?
Refer to “4. Installation”.
note4)
User program is User-made S/W for PC.
z
ERR LED is working
State
Corrective Measures
Blinking intermittently
In case that the option card is receiving wrong data due to Noise or
other causes. It is normal.