Chapter 8 Trouble Shooting
8-11
8.2.8 Communication error with master
Communication error with master
Yes
Check HSL parameter
Is
HSL
parameter
setting
proper?
No
Check the power of slave and
master module
Yes
Do you supply power to slave
and master module?
Is slave station No. setting
overlapped?
Does cable connection have
error?
Dose cable terminal have
terminal resistor?
Is
operating
environment
proper?
Check the slave module station
No. and SyCon station No.
Stick module to slot strongly
Stick terminal resistor (121
Ω) to
edge of trunk line
Check the standard cable and
length
Contact to A/S center
No
Yes
Yes
No
No
Yes
Yes
No
No
Do you use combined cable?
Use standard individual cable
No
Yes