Chapter 3 Product Installation and trial operation
3-18
1) TCP/IP setting(XGK/I CPU series)
Classification
Content
Station No
Station number used for high speed link and RAPIEnet communication between
Ethernet modules.
Modules on the same network should not have duplicate station numbers.
- The station number range of the high speed link communication is 0 ~ 63.
- The station number range of the RAPIEnet communication (including Smart
Extension) is 0 ~ 220.
* Precautions for V6.0 and later
- When RAPIEnet is enabled, it is set as RAPIEnet's station number.
- When using Modbus RTU / ASCII and XGT Cnet server service, it is set as
station number.
Media
Select the communication media you want to use.
AUTO(electric): Automatically sets the media settings of the currently installed
module.
10M/HALF: 10Mbps Half Duplex Electric
10M/FULL: 10Mbps Full Duplex Electric
100M/HALF: 100Mbps Half Duplex Electric
100M/FULL: 10Mbps Full Duplex Electric
100M/FX/HALF: 100Mbps Half Duplex optical
100M/FX/FULL: 100Mbps Full Duplex optical
1G/FULL: 1Gbps Full Duplex Electric
1G/FX/FULL: 1Gbps Full Duplex optical
IP address
Set the IP address of the Ethernet module.
Subnet mask
This is the value for classifying whether the destination station is in the same
network with its own station or not.
Gateway
Set the gateway module address (router address) for sending and receiving data
through a station or a public network that uses a different network from your own
station.
DNS Server
Specifies the domain name server.
DHCP
DHCP (Dynamic Host Configuration Protocol) is used when you want to use
dynamic IP (use when connecting ADSL line) without using Fixed IP.
Relay
Used to send data frames received on the port to the other port.
OPC UA
Enable / Disable the OPC UA server function.(Only V7.x version is supported)
No. of Dedicated
Connections
The maximum number of TCP-dedicated services that can be connected at the
same time.
- V6.0 or less version: Available range is 1~ 16 and default is 3.
- V6.0 or higher version: The number of server connections that can be connected
simultaneously is 64, and is not affected by the number of dedicated connections
in the basic parameters.
2) Setting timeout time
Classification
Content
When operating
Client
If a response message is not received within the client Receive Time Out period
set by the requesting server during P2P client communication, it assumes a
problem with the server system and terminates the connected P2P client service.
- V6.0 or less version: Not Available
- V6.0 or higher 2 sec~255 sec setting available. (If the client driver type is
RAPIEnet, 4 seconds are applied.
On Server Mode
If there is no request for the set time from the client while the server service is
connected to the PC or HMI , the server operation is finished assuming that a
problem has occurred with the client system.
Содержание XGL-EFMF
Страница 17: ...Table of Content 16 ...
Страница 27: ...Chapter 1 Overview 1 10 ...
Страница 39: ...Chapter 2 Product specifications 2 12 4 XOL ES4T XOL ES4H 2 1 3 3 4 5 6 7 8 9 10 ...
Страница 108: ...Chapter 4 Smart Extension service 4 19 The opposite case is indicated by a blue line ...
Страница 135: ...Chapter 4 Smart Extension service 4 46 ...
Страница 174: ...Chapter 5 High speed link service 5 35 ...
Страница 197: ...Chapter 6 P2P service 6 14 Then select Online Change Mode to run ...
Страница 227: ...Chapter 6 P2P service 6 44 ...
Страница 289: ...Chapter 7 server service 7 62 ...
Страница 358: ...Appendix A 25 A 6 Dimension 1 XGL EFMTB EFMFB XGL EH5T Unit mm ...
Страница 359: ...Appendix A 26 2 XOL ES4H Unit mm ...
Страница 360: ...Appendix A 27 3 XOL ES4T Unit mm ...
Страница 361: ...Appendix A 28 ...
Страница 363: ...Warranty and Environment Policy 2 ...